Beretta POWER MAX BOX 130-2 P Installation Manual page 71

Modular system
Hide thumbs Also See for POWER MAX BOX 130-2 P:
Table of Contents

Advertisement

For all models
- Open the general fuel shut-off valve.
- Open the tap of the unit you are working on.
- Place the main system switch, the main switch of the module
and the one of the unit on which you are working on "ON".
- Make sure that there is no heat or DHW demand.
It is now necessary to change the setting of the parameter 98.
Proceed as follows:
- On the home screen of the control panel, press the ● key
- Select "Settings" with the ▲ / ▼ keys and press the ● key
- Select "Device configuration" with the ▲ / ▼ keys and press
the ● key
Settings
"
"
Boiler Settings
"
"
Clock Settings
"
"
PB Configuration
"
"
Appliance Configuration
"
- Enter the password as described in paragraph "Password ac-
cess"
- Select the unit between "Master" and "Dep1 ... N"
- Press the ▼ key, select "(98) Appliance Settings" and press
the ● key
Appliance Configuration
"
( 97) IO Configuration
"
"
(98) Appliance Settings
"
"
Configuration Confirmed
"
- With the ▲ / ▼ keys change the value following what is in the
following table and press the ● key:
Model
130-2 P
Power Max BOX
160-2 P
Power Max BOX
200-2 P
Power Max BOX
260-2 P
Power Max BOX
300-2 P
Power Max BOX
330-3 P
Power Max BOX
390-3 P
Power Max BOX
450-3 P
Power Max BOX
520-4 P
Power Max BOX
600-4 P
Power Max BOX
"
"
1
2
No
"
"
"
Parameter 98
12
10
8
4
2
6
4
2
4
2
- Press the ▼ key, select "Config. Confirmed" and press the ●
key
- With the ▲ / ▼ keys change the value to "Yes" and press the
● key
Appliance Configuration
"
( 97) IO Configuration
"
"
(98) Appliance Settings
"
"
Configuration Confirmed
"
At this point the systems starts an application update process. Once
this is finished, the menu "Settings" appears on the menu.
Repeat this operation for all the modules.
- Press ◄ until you return to the home screen
An error message is displayed for a few seconds and then the display
returns to its normal state.
Apply the new gas label supplied in the kit on completion of the con-
version.
Gruppo termico regolato per:
G30 - G31 28-30/37 mbar
Paese di destinazione:
After installing the accessory, check all gaskets tightness.
Carry out all calibration activities described in Paragraph "Adjust-
ments".
Restore the desired set points.
"
1
4
Yes
"
"
"
71

Advertisement