The parameters regulating such temperature are:
Par.
Description
No.
Sets the desired flow temperature with heating mode.
3
Active for the heating mode Par. 1 = 0 o 3
Limits the minimum value that can be assigned to the set-
23
point in heating mode (does not apply to heating mode 4).
Limits the maximum value that can be assigned to the set-
24
point in heating mode (does not apply to heating mode 4).
Delivery Temp.
(°C)
Par. 24
Par. 03
Par. 23
Mode 1
(Climatic functioning with room/heat demand thermostat, variable set
point according to the outdoor temperature)
In this case the thermal module operates with a variable set-point de-
pending on outdoor temperature based on a climatic curve defined
by the following parameters:
Par.
Description
No.
Defines the value of the set point calculated on climatic
109
mode (Par. 1 = 1).
Establishes the max. set-point at the minimum outdoor
19
temperature for climatic regulation
Establishes the minimum outdoor temperature to which
20
the maximum set-point can be associated for climatic
regulation
Establishes the minimum set-point at the maximum out-
21
door temperature for climatic regulation
Establishes the maximum minimum outdoor temperature
22
to which the minimum set-point can be associated for
climatic regulation
Limits the minimum value that can be assigned to the set-
23
point in heating mode (does not apply to heating mode 4).
Limits the maximum value that can be assigned to the set-
24
point in heating mode (does not apply to heating mode 4).
Defines the temperature at which climatic regulation is
25
switched off
Delivery Temp.
Par. 24
Par. 19
Par. 21
Par. 23
Tset max (°C)
The demand is activated when the room/heat demand thermostat's
Setpoint
contact is closed provided that outdoor temperature does not exceed
the value set by the parameter 25.
if the outdoor temperature is higher than the one set on parameter 25
Tset min (°C)
, the burner is stopped even if there is a heat demand.
The climatic curve can also be adjusted in a simpler, more us-
er-friendly way.
Outdoor Temp. (°C)
Enter the "CH" menu. The following display will appear:
Central Heating (CH)
"
Outdoor reset
"
Press the ● key to confirm and enter the climatic curve screen.
Outdoor reset
"
"Design Supply Temp." and "Design Outdoor Temp." will be dis-
played. To change their value, press the ● key.
Use the ▲ / ▼ keys to modify Design Supply Temp and the ◄ /
1
► keys to change Design Outdoor Temp.
Press ● to save changes
2
Use the ◄ / ► keys to select other values.
3
Repeat steps 1 from 3 to make other changes.
After setting the parameters, press the ESC key to exit the menu.
b
If the outdoor temperature sensor (accessory) is not detected
(not installed or damaged) the system provides a warning: no.
202
The presence of the warning does not stop the thermal module
allowing a heat request to be carried out at the maximum setpoint
set on the climatic regulation.
(°C)
Par. 20
Par. 22
"
"
"
90
0
-15
35
T Outside [°C]
"
"
Tset max (°C)
Par. 109
Tset min (°C)
Par. 25
Outdoor Temp. (°C)
Des. Supply T.
82.0
°C
"
"
"
"
Bas. Supply T.
40.0
°C
"
"
"
"
WW Shutdown
21.0
°C
"
"
"
"
Bas. Outd. T.
21.0
°C
"
"
"
"
Des. Outd. T.
-4.0
°C
"
"
"
"
59