Beretta POWER MAX BOX 130-2 P Installation Manual page 53

Modular system
Hide thumbs Also See for POWER MAX BOX 130-2 P:
Table of Contents

Advertisement

Display
Par.
Menu
visualis-
No.
ation
The value of this parameter is defined by
121 Prog Input
M1
6.
The value of this parameter is defined by
Prog Input
M1
122
7.
The value of this parameter is defined by
Prog Input
M1
123
8.
The value of this parameter is defined by
Prog.
M1
124
Input RT.
The value of this parameter is defined by
Prog.
M1
125
Output 1.
The value of this parameter is defined by
Prog.
M1
126
Output 2.
The value of this parameter is defined by
Prog.
M1
127
Output 3.
The value of this parameter is defined by
Prog.
M1
128
Output 4.
Flow
M1
129
Defines the type of flow sensor used.
sensor
Mod.
Defines the delta T set for the operation of
M1
133
Pump dT
Description
Par. 97.
0 = Disabled
1 = T_Flue sensor
2 = Flue switch
3 = APS switch
Par. 97.
0 = Disabled
1 = T_Flue_2 sensor
2 = T_Flue_2 + Bl. Flue
3 T_System sensor
4 = Blocked Flue switch 5 Cascade
Sensor
Par. 97.
0 = Disabled
1 = T_DCW sensor
2 = Water pressure switch
Par. 97.
0 = Disabled
1 = Enabled
Par. 97.
0 = Disabled
1 = General Pump
2 = CH Pump
3 = DHW Pump
4 = System Pump
5 = Cascade Pump
6 = Alarm Relay
7 = Filling Valve
8 = LPG Tank
9 = External Igniter
10 = Air Damper
14 = Alarm Burner CC
15 = Status Burner CC
17 = Antilegionella pump
Par. 97.
0 = Disabled
1 = General Pump
2 = CH Pump
3 = DHW Pump
4 = System Pump
5 = Cascade Pump
6 = Alarm Relay
7 = Filling Valve
8 = LPG Tank
9 = External Igniter
10 = Air Damper
14 = Alarm Burner CC
15 = Status Burner CC
17 = Antilegionella pump
Par. 97.
0 = Disabled
1 = General Pump
10 = Air Damper
11 = External Igniter
12 = Modulating Pump
Par. 97.
0 = Disabled
1 = General Pump
2 = CH Pump
3 =DHW Pump
4 = System Pump
5 = Cascade Pump
6 = Alarm Relay
7 = Filling Valve
8 = LPG Tank
the modulating circulator.
Default
Range
setting
Defined by
0,1,2,3
Par. 97
Defined by
0,1,2,3,4,5
Par. 97
Defined by
0,1,2
Par. 97
Defined by
0,1
Par. 97
0,1,2,3,4,5,6,7,
Defined by
8,9,10,14,15,17
Par. 97
0,1,2,3,4,5,6,7,
Defined by
8,9,10,14,15,17
Par. 97
Defined by
0,1,10,11,12
Par. 97
0,1,2,3,
Defined by
4,5,6,7,8
Par. 97
Bitron, Huba: DN8,
DN10, DN15,
Huba DN25
DN15, DN20, DN25
5...40
15
Access
UM
Category
type
I
General
I
General
I
General
I
General
I
General
I
General
I
General
I
General
I
General
°C
I
General
53