Vega WEIGHTRAC 31 Operating Instructions Manual page 45

Radiation-based sensor for mass flow detection
Hide thumbs Also See for WEIGHTRAC 31:
Table of Contents

Advertisement

Setup/Adjustment (step
6)
WEIGHTRAC 31 • 4 ... 20 mA/HART - four-wire
distance of at least 3 m (10 ft) to the sensor for measurement of the
background radiation. A source container with a Co-60 source should
have a distance at least 5 m (17 ft).
This ensures that the measured pulse rate really originates from the
source used.
Fig. 29: Adjustment
In this menu item you can enter the measuring range (min. and max.
process value) of the sensor.
These settings influence the current output of the sensor.
Enter in the menu window "Max. process value" the max. level (full),
for example in "t/h". This corresponds to an output current of 20 mA.
Enter in the menu window "Min. process value" the min. level (empty),
for example in "t/h". This corresponds to an output current of 4 mA.
7 Setup with PACTware
45