Advertisement

5 Connecting to power supply
Adjustment and connec-
tion compartment - In-
struments with intrinsi-
cally safe current output
Electronics and terminal
compartment - summa-
tion
28
( )
1
Fig. 15: Adjustment and connection compartment (Ex-ia) with instruments with
intrinsically safe current output
1
Terminals for intrinsically safe signal output 4 ... 20 mA/HART active (not on
versions with Ex-d approval)
2
Contact pins for the display and adjustment module or interface adapter
3
Terminals for the external display and adjustment unit
4
Ground terminal
5.3

Connection - Summation

Several instruments can be cascaded to measure also broad con-
veyor belts. The measuring ranges of the instruments must overlap.
Cascading means that two or several instruments are connected
which can together cover a longer measuring range.
The instrument acts as Master and all other instruments operate as
Slaves.
The pulse rates of all instruments are summed in the Master instru-
ment and converted into a common signal.
The Master instrument must have the function "Mass flow detection".
For this purpose, select under the menu item "Setup/Application" the
function "Mass flow detection".
Set the address setting (MGC) on the Master instrument to "0 - 0".
For this purpose, the Slave instruments must be defined as "Slave".
Select under the menu item "Setup/Application" the function "Sum-
mation Slave".
The address setting (MGC) on the Slave instruments can be freely
selected. Only the address "0 - 0" is reserved for the Master instru-
ment.
Connect the instruments according to the following wiring plan:
+
1
2
6 7 8
5
(-)
WEIGHTRAC 31 • 4 ... 20 mA/HART - four-wire
2
3
4