UPS5000-E-(600 kVA-800 kVA)
User Manual
Figure 3-72 Connecting cables to a 1+1 parallel system (800 kVA)
(1) Mains input power
cables
Figure
for a bus system consisting of two UPS systems respectively.
The length and specifications of power cables on each UPS must be the same to achieve
current equalization in bypass mode. The power cables include bypass input power cables and
UPS output power cables.
Issue 02 (2016-01-20)
(2) Bypass input power
cables
3-73,
Figure
3-74, and
Figure 3-75
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
(3) Battery
cables
show the conceptual diagram and cable connections
3 Installation
(4) Output power
cables
104