UPS5000-E-(600 kVA-800 kVA)
User Manual
If you do not close the input surge protection circuit breaker (if any on the input PDC), the system can
start properly but will generate an alarm, asking you to close the input surge protection circuit breaker.
Step 2 After the LCD starts, perform the following steps:
After you specify the settings, the Bypass mode and No battery alarms are displayed on the LCD.
The main buttons on the Settings Wizard screen are described as follows:
1.
2.
Set the date and time correctly. Incorrect time display in running and alarm information would
lead to analysis errors during maintenance or repair.
Issue 02 (2016-01-20)
To power on a UPS in standard configuration (configured only with an internal
maintenance bypass switch), perform the following operations:
a.
Turn on the external bypass and mains input switches.
b.
Close the external input surge protection circuit breaker (if any).
The UPS starts initialization. The LCD displays the Huawei logo and an
initialization progress bar.
If the UPS is starting for the first time, set the language, date and time, network
parameters, and system parameters on the Settings Wizard screen.
If this is not the first startup, retain the previous settings.
Tap Previous to return to the upper-level screen.
Tap Next to go to the next screen.
Tap Cancel to exit the Settings Wizard screen.
Various languages are available, such as Chinese and English. Press Down and Up to
view the language types, as shown in
Figure 5-4 Language screen
After selecting the language, tap Next to open the date and time setting page. Select the
date format, for example, YYYY-MM-DD. See
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Figure
5-4.
Figure
5-5.
5 Operations
181