UPS5000-E-(600 kVA-800 kVA)
User Manual
Figure 5-56 Parameters associated with intelligent power on the LCD (6)
Table 5-2
Table 5-2 Parameters associated with intelligent power
Parameter
Working mode
D.G. mode
Intra-rack power module
start delay (s)
Input adaptability
Output freq. track rate
(Hz/s)
D.G. connection [GEN]
MUS05A DO_4
ATS
D.G. startup batt. volt.
(V/cell)
D.G. power limiting
(kVA)
D.G. charger power ratio
(%)
Issue 02 (2016-01-20)
lists the parameters associated with intelligent power.
Value
ECO
Enable
5
Strong
0.6
Enable
D.G. control
Connected
1.80
N/A
N/A
In battery mode (not battery test state), when the battery voltage reaches D.G. startup batt. volt. or
Low battery voltage, the UPS triggers D.G. startup signals.
In normal mode or bypass mode, if the mains is normal (the mains supplies power for 1 minute and
the D.G. runs for 15 minutes), the UPS triggers D.G. shutdown signals.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Operations
Remarks
N/A
You cannot change the value.
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Indicates the actual D.G.
power. Set it as required.
Indicates the percentage of the
battery power provided by the
charger. Set it as required.