UPS5000-E-(600 kVA-800 kVA)
User Manual
Figure 5-34 Turning on the maintenance bypass switch (600 kVA UPS in standard configuration)
Figure 5-35 Maint. breaker closed alarm
After the UPS transfers to maintenance bypass mode, the Maint. breaker closed and Bypass mode
alarms are displayed on the LCD.
Issue 02 (2016-01-20)
The preceding figure uses the 600 kVA UPS in standard configuration as an example. The operations
are the same for the 600 kVA UPS in full configuration and the 800 kVA UPS.
Exercise force when turning on or off the bypass maintenance switch.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Operations