UPS5000-E-(600 kVA-800 kVA)
User Manual
If the power module receives a startup command when it cannot be started, the startup command will be
kept for 1 minute. If the startup command is not cleared within 1 minute (for example, other faults occur
on the module, or you perform shutdown or rectify faults) and the module can be started, the module
responds to the startup command.
Step 6 Ensure that the UPS transfers to normal mode. View the system running diagram to check that
the Bypass mode alarm disappears on the LCD. Check the UPS three-phase output voltage
and frequency by viewing the AC output on the LCD, as shown in
5-15. Use a multimeter to measure the three-phase output voltage and frequency.
The three-phase output voltage should be 220 V, 230 V, or 240 V, and the frequency should be 50 Hz or
60 Hz.
Check on the LCD. See
Issue 02 (2016-01-20)
Figure 5-12 Login
Table 4-4
lists the default user names and preset passwords and describes the permission of the
default users.
If you enter incorrect passwords for three consecutive times, you will be locked out for 5 minutes.
e.
On the homepage, choose Monitoring > Control, and click Inv. ON. In the
displayed dialog box, click OK to start the inverter, as shown in
Figure 5-13 Starting the inverter
Figure 5-14
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
and
Figure
5-15.
5 Operations
Figure
5-13.
Figure 5-14
and
Figure
187