You can set hibernation mode on the LCD or WebUI.

5.2.1 LCD

Procedure
Step 1 On the main screen, tap System Info and
Step 2 Tap Advanced Param.. Tap
5-45.
Figure 5-45 Hibernation parameters on the LCD
Step 3 On the LCD, set Paral. sys. hibernate to Enable. A confirmation message and security
warning are displayed, as shown in
Issue 02 (2016-01-20)
Before you start hibernation mode, ensure that the load power is stable. When the system
load power fluctuation is greater than the rated capacity of half a module (for example, the
single-phase load fluctuation is greater than 6.67 kVA for a 40 kVA module), the UPS may
enter and exit from hibernation mode repeatedly.
Before you start hibernation mode, check that the number of redundant power modules
and racks are appropriate. If the number is insufficient, the UPS may not enter hibernation
mode.
If you have not logged in, enter a user name and password, and tap