Vega POINTRAC 31 Operating Instructions Manual page 30

8/16 ma/hart - four-wire
Table of Contents

Advertisement

6 Set up with the indicating and adjustment module
Diagnosis/Simulation
Diagnosis/Calculated
damping
Additional settings/PIN
30
In this menu item you can simulate measured values via the current
output. This allows the signal path to be tested, e.g. via connected
indicating instruments or the input card of the processing system.
You can simulate different values:
Pulse rate of the sensor
Current output
Switching function of the relay
Information:
The simulation is terminated automatically 60 minutes after the last key
has been pushed.
The sensor calculates automatically a suitable integration time.
Further settings
In this menu item, the PIN is permanently activated/deactivated. Thus
you protect the sensor data against unauthorized access and
unintended changes. The default setting of the PIN is 0000.
POINTRAC 31 • 8/16 mA/HART - four-wire