Summary of Contents for Vega POINTRAC 31

  • Page 1: Operating Instructions

    Operating Instructions Radiation-based sensor for level detection POINTRAC 31 Foundation Fieldbus Document ID: 41779...
  • Page 2: Table Of Contents

    Diagnostics and servicing Maintenance ........................37 Status messages ......................37 Rectify faults ........................40 Exchanging the electronics module ................41 Software update ......................42 How to proceed if a repair is necessary ................42 10 Dismount POINTRAC 31 • Foundation Fieldbus...
  • Page 3 11.4 Industrial property rights ....................57 11.5 Trademark ........................57 Safety instructions for Ex areas Take note of the Ex specific safety instructions for Ex applications. These instructions are attached as documents to each instrument with Ex approval and are part of the operating instructions manual. Editing status: 2016-04-18 POINTRAC 31 • Foundation Fieldbus...
  • Page 4: About This Document

    Action This arrow indicates a single action. Sequence of actions Numbers set in front indicate successive steps in a procedure. Battery disposal This symbol indicates special information about the disposal of bat- teries and accumulators. POINTRAC 31 • Foundation Fieldbus...
  • Page 5: For Your Safety

    During work on and with the device the required personal protective equipment must always be worn. Appropriate use The POINTRAC 31 is a sensor for point level detection. You can find detailed information about the area of application in chapter "Product description". Operational reliability is ensured only if the instrument is properly used according to the specifications in the operating instructions manual as well as possible supplementary instructions.
  • Page 6: Ce Conformity

    That is why we have introduced an environment management system with the goal of continuously improving company environmental pro- tection. The environment management system is certified according to DIN EN ISO 14001. Please help us fulfil this obligation by observing the environmental instructions in this manual: • Chapter "Packaging, transport and storage" • Chapter "Disposal" POINTRAC 31 • Foundation Fieldbus...
  • Page 7: Product Description

    Alternatively, you can access the data via your smartphone: • Download the smartphone app "VEGA Tools" from the "Apple App Store" or the "Google Play Store" • Scan the Data Matrix code on the type label of the instrument or •...
  • Page 8: Principle Of Operation

    When the intensity of the radiation drops below a defined value, e.g. due to damping, then the POINTRAC 31 switches. The measuring principle has proven itself well under extreme conditions because it measures contactlessly from outside through the vessel wall. The measuring system ensures maximum safety, reliability and plant availability independent of the medium and its properties.
  • Page 9: Accessories And Replacement Parts

    PACTware with VEGA-DTM is required. You can find further information in the operating instructions "Interface adapter VEGACONNECT" (Document-ID 32628). VEGADIS 81 The VEGADIS 81 is an external display and adjustment unit for VEGA plics sensors. ® For sensors with double chamber housing the interface adapter "DISADAPT"...
  • Page 10 He is responsible that the radiation protection ordinance is maintained and that all radiation protection measures are implemented. Control area Control areas are areas in which the local dose rate exceeds a certain value. Only persons who undergo official dose monitoring are allowed into these control areas. You can find the respectively valid limit values POINTRAC 31 • Foundation Fieldbus...
  • Page 11 (in Ger- many, for example, the radiation protection ordinance). We are at your disposal for further information concerning radiation protection and regulations in other countries. POINTRAC 31 • Foundation Fieldbus...
  • Page 12: Mounting

    In the case of instrument housings with self-sealing NPT threads, it is not possible to have the cable entries screwed in at the factory. The free openings for the cable glands are therefore covered with red dust protection caps as transport protection. POINTRAC 31 • Foundation Fieldbus...
  • Page 13: Mounting Instructions

    The following mounting information is applicable as long as there is nothing else specified in the "Source Sizing" document. Fig. 3: Mounting position - level detection - version with detector tube Vertical mounting Mounting horizontally, at right angles to container POINTRAC 31 • Foundation Fieldbus...
  • Page 14 Sensor orientation Level detection - max. detection The POINTRAC 31 is suitable for level detection in liquids or bulk solids. It is mounted at the height of the requested switching point. POINTRAC 31 • Foundation Fieldbus...
  • Page 15 4 Mounting Fig. 5: POINTRAC 31 as max. level detection (uncovered) Level detection - min. detection Fig. 6: POINTRAC 31 as min. level detection (covered) POINTRAC 31 • Foundation Fieldbus...
  • Page 16 Bulk solids with low density Fig. 7: POINTRAC 31 as level detection (top view) POINTRAC 31 lends itself well for level detection of bulk solids with low density. Mount the instrument horizontally at the height of the requested switching point. Mount the source container VEGASOURCE displaced by 90° in order to get the widest possible radiation angle.
  • Page 17: Connecting To Power Supply

    You have to remove these plugs before electrical connection. NPT thread In the case of instrument housings with self-sealing NPT threads, it is not possible to have the cable entries screwed in at the factory. The POINTRAC 31 • Foundation Fieldbus...
  • Page 18 3. Remove approx. 10 cm (4 in) of the cable mantle, strip approx. 1 cm (0.4 in) of insulation from the ends of the individual wires 4. Insert the cable into the sensor through the cable entry POINTRAC 31 • Foundation Fieldbus...
  • Page 19 8. Connect the screen to the internal ground terminal, connect the external ground terminal to potential equalisation 9. Tighten the compression nut of the cable entry gland. The seal ring must completely encircle the cable 10. Screw the housing lid back on The electrical connection is finished. POINTRAC 31 • Foundation Fieldbus...
  • Page 20: Connection

    Signal input 4 … 20 mA (active sensor) Switching input for NPN transistor 6 Switching input floating Transistor output Interface for sensor-sensor communication (MGC) Simulation switch (1 = simulation on) 10 Setting the bus address for sensor-sensor communication (MGC) MGC = Multi Gauge Communication POINTRAC 31 • Foundation Fieldbus...
  • Page 21 Signal input 4 … 20 mA (active sensor) Switching input for NPN transistor 5 Switching input floating Transistor output Interface for sensor-sensor communication (MGC) Simulation switch (1 = simulation on) Setting the bus address for sensor-sensor communication (MGC) MGC = Multi Gauge Communication POINTRAC 31 • Foundation Fieldbus...
  • Page 22 Fig. 12: Adjustment and connection compartment (Ex-ia) with instruments with intrinsically safe current output Terminals for intrinsically safe signal output FF bus Contact pins for the display and adjustment module or interface adapter Terminals for the external display and adjustment unit Ground terminal POINTRAC 31 • Foundation Fieldbus...
  • Page 23: Set Up With The Display And Adjustment Module

    The display and adjustment module is powered by the sensor, an ad- ditional connection is not necessary. Fig. 13: Insert display and adjustment module Note: If you intend to retrofit the instrument with a display and adjustment module for continuous measured value indication, a higher lid with an inspection glass is required. POINTRAC 31 • Foundation Fieldbus...
  • Page 24: Adjustment System

    1 s, the value or position changes continuously. When the [OK] and [ESC] keys are pressed simultaneously for more than 5 s, the display returns to the main menu. The menu language is then switched over to "English". POINTRAC 31 • Foundation Fieldbus...
  • Page 25: Parameter Adjustment

    Stick with the normal sequence of the menu items as closely as pos- sible. Setup Setup - Isotope In this menu item you can adjust the POINTRAC 31 to the integrated isotope in the source container. For this purpose, check which isotope is integrated in the source container. You can find this information on the type label of the source container.
  • Page 26 The normal reduction of the emitter activity is hence considered through the radioactive decay. The POINTRAC 31 requires this information of the automatic decay compensation. This ensures an interference-free measurement over the complete life time of the gamma emitter - an annual recalibration is not necessary.
  • Page 27 (single point adjustment" as adjustment mode (Setup/Adjustment mode). adjustment) In this menu item you determine the point at which the POINTRAC 31 should switch in uncovered status. Empty the vessel until the sensor is uncovered. For this enter the requested pulse rate manually or let the rate be determined by POINTRAC 31.
  • Page 28 POINTRAC 31. Automatic determination of the pulse rate should be given preference. You can enter the adjustment point (ct/s) manually. You can let the adjustment point be determined by POINTRAC 31. Adjustment "uncovered" This menu item appears only if you have selected under adjustment (two-point adjustment) mode (setup/adjustment mode) the "Two-point adjustment".
  • Page 29 POINTRAC 31. Automatic determination of the pulse rate should be given preference. You can enter the adjustment point (ct/s) manually. You can let the adjustment point be determined by POINTRAC 31. Setup - Relay In this menu item you can select which mode the sensor should oper- ate in.
  • Page 30 Note: To carry out a simulation with the display and adjustment module, you have to switch on the simulation switch on the electronics module (switch position 1). You can find the rotary switch on the electronics module in the elec- tronics and connection department (large cover). You can simulate different values: POINTRAC 31 • Foundation Fieldbus...
  • Page 31 When a reset is carried out, all settings (with only a few exceptions) - Reset are reset. The exceptions are: PIN, language, SIL and HART mode. The following reset functions are available: Basic settings: Resetting of the parameter adjustments to default values at the time of shipment. Order-specific settings are deleted. POINTRAC 31 • Foundation Fieldbus...
  • Page 32 If the measured value is outputted via the 4 … 20 mA output, you must not switch over to HART Multidrop. The mode 'Standard', with fixed address 0 (factory setting), means output of the measured value as 8/16 mA signal. This parameter is described in the operating instructions manual "Display and adjustment module". POINTRAC 31 • Foundation Fieldbus...
  • Page 33: Saving The Parameter Adjustment Data

    If it is necessary to exchange a sensor, the display and adjustment module is inserted into the replacement instrument and the data are likewise written into the sensor via the menu item "Copy sensor data". POINTRAC 31 • Foundation Fieldbus...
  • Page 34: Setup With Pactware

    A description of the update procedure is also available in the Internet. Further setup steps are described in the operating instructions manu- al "DTM Collection/PACTware" attached to each DTM Collection and POINTRAC 31 • Foundation Fieldbus...
  • Page 35: Saving The Parameter Adjustment Data

    The standard version is available as a download under www.vega.com/downloads and "Software". The full version is avail- able on CD from the agency serving you. Saving the parameter adjustment data We recommend documenting or saving the parameter adjustment data via PACTware.
  • Page 36: Set Up With Other Systems

    This software is updated via the Internet and new EDDs are automatically taken over into the device catalogue of this software after they are released by the manufacturer. They can then be transferred to a Field Communicator. POINTRAC 31 • Foundation Fieldbus...
  • Page 37: Diagnostics And Servicing

    This status message is inactive by default. It can be activated by the user via PACTware/DTM or EDD. Out of specification: The measured value is unstable because the instrument specification is exceeded (e.g. electronics temperature). This status message is inactive by default. It can be activated by the user via PACTware/DTM or EDD. Maintenance: Due to external influences, the instrument function is limited. The measurement is affected, but the measured value is POINTRAC 31 • Foundation Fieldbus...
  • Page 38 – Error in the internal instru- – Carry out a reset ment communication – Exchanging the electronics EPROM data error F036 – Error during software – Repeat software update update – Exchanging the electronics Faulty pro- gram memory POINTRAC 31 • Foundation Fieldbus...
  • Page 39 Function check The following table shows the error codes and text messages in the status message "Function check" and provides information on causes as well as corrective measures. POINTRAC 31 • Foundation Fieldbus...
  • Page 40: Rectify Faults

    PACTware and suitable DTM. In many case, the failure reasons can thus be determined and faults rectified. Check output signal The following table describes possible faults that may not generate an error message: POINTRAC 31 • Foundation Fieldbus...
  • Page 41: Exchanging The Electronics Module

    Should these measures not be successful, please call in urgent cases 24 hour service hotline the VEGA service hotline under the phone no. +49 1805 858550. The hotline is also available outside normal working hours, seven days a week around the clock.
  • Page 42: Software Update

    Clean the instrument and pack it damage-proof • Attach the completed form and, if need be, also a safety data sheet outside on the packaging • Please contact the agency serving you to get the address for the return shipment. You can find the agency on our home page www.vega.com. POINTRAC 31 • Foundation Fieldbus...
  • Page 43: Dismount

    Pass the instrument directly on to a spe- cialised recycling company and do not use the municipal collecting points. These may be used only for privately used products according to the WEEE directive. POINTRAC 31 • Foundation Fieldbus...
  • Page 44: Supplement

    Input variable Measured variable The measured variable is the intensity of the gamma radiation. When the intensity of the radiation is below the stipulated value due to a damping by the medium, the POINTRAC 31 switches. POINTRAC 31 • Foundation Fieldbus...
  • Page 45 Ʋ Channel 8 Electronics temperature Ʋ Channel 9 Pulse rate Transmission rate 31.25 Kbit/s Current value 10 mA, ±0.5 mA Resolution, digital > 0.1 mm (0.004 in) Relay output Output Relay output (SPDT), floating spdt Switching voltage Ʋ Min. 10 mV POINTRAC 31 • Foundation Fieldbus...
  • Page 46 With temperatures of more than 60 °C we recommend the use of water cooling Vibration resistance mechanical vibrations up to 1 g in the frequency range 5 … 200 Hz Tested according to the guidelines of German Lloyd, GL directive 2. POINTRAC 31 • Foundation Fieldbus...
  • Page 47 Via the digital output signal - depending on the electron- ics version Range -40 … +85 °C (-40 … +185 °F) Resolution < 0.1 K Accuracy ±3 K Voltage supply Operating voltage Ʋ Sensor power supply 20 … 72 V DC or 20 … 253 V AC, 50/60 Hz POINTRAC 31 • Foundation Fieldbus...
  • Page 48: Supplementary Information Foundation Fieldbus

    Instruments with approvals can have different technical specifications depending on the version. For that reason the associated approval documents of these instruments have to be carefully noted. They are part of the delivery or can be downloaded under www.vega.com, "VEGA Tools" and "Instrument search" as well as in the download area.
  • Page 49 Density with Temperature correction FF_VAPOR_DENSI- TY_UNIT FF_VAPOR_DENSITY Selected unit code for “FF_VAPOR_DENSITY” _UNIT FF_PROCESS_TEM- Process temperature FF_PROCESS_TEM- PERATURE PERATURE_UNIT FF_PROCESS_TEM- Selected unit code for “FF_PROCESS_TEMPER- PERATURE_UNIT ATURE” FF_DENSITY Density FF_DENSITY_UNIT FF_DENSITY_UNIT Selected unit code for “FF_DENSITY” POINTRAC 31 • Foundation Fieldbus...
  • Page 50 Selected unit code for process temperature DELTA_I Calculated percent delta I GAUGE_TEMPERA- Electronics temperature TURE DECAY_COMPENSA- Factor for the decay compensation TION_FACTOR PMT_VOLTAGE_CALI- Photomultiplier voltage on delivery BRATION CORRELATION_CO- Correlation coefficient for linearizer table ERROR_TEXT Error text PMT_VOLTAGE_AC- Current photomultiplier voltage TUAL POINTRAC 31 • Foundation Fieldbus...
  • Page 51 Transducer block is in mode "Manual" 0x44 Uncertain Last Usable Value Three or more internal communications have failed while "Process Data Update". Last usable value is displayed 0x48 Uncertain Substitute On user error codes: 29 POINTRAC 31 • Foundation Fieldbus...
  • Page 52 Undefined 19 Detector temperature critical OUT_OF_SPEC Error while auto-standardization FAILURE Excessive radiation 123, 124 FAILURE Input out of bounds OUT_OF_SPEC Error while signal processing FAILURE Undefined 13 Undefined 12 Undefined 11 Undefined 10 Undefined 9 Undefined 8 AITB simulated FUNCTION_CHECK Undefined 6 Undefined 5 Undefined 4 Undefined 3 POINTRAC 31 • Foundation Fieldbus...
  • Page 53: Dimensions

    Not displayed 33, 45, 71, 86 11.3 Dimensions The following dimensional drawings represent only an extract of all possible versions. Detailed dimensional drawings can be downloaded at www.vega.com/downloads under "Drawings". Aluminium and stainless steel housing M20x1,5/ 119 mm ½ NPT (4.69")
  • Page 54 ø 76,2 mm (3") Fig. 21: POINTRAC 31 with detector tube - measuring length: 152 mm or 304 mm (6 in/12 in) Measuring range = Order length 152 mm or 304 mm (6 in/12 in) POINTRAC 31 • Foundation Fieldbus...
  • Page 55 (0.55") (0.56") Fig. 22: POINTRAC 31 with detector tube, 152 mm or 304 mm (6 in/12 in) - with supplied mounting accessories POINTRAC 31 without detector tube Fig. 23: POINTRAC 31 without detector tube - measuring range = order length 50 mm (2 in)
  • Page 56 POINTRAC 31 - Mounting example 111 mm (4.37") 195 mm (7.68") 152,5 mm (6.00") 127 mm (5.00") 51 mm (2.01") 14 mm (0.55") Fig. 24: POINTRAC 31 without detector tube, 50 mm (2 in) - supplied mounting accessories POINTRAC 31 • Foundation Fieldbus...
  • Page 57: Industrial Property Rights

    Les lignes de produits VEGA sont globalement protégées par des droits de propriété intellec- tuelle. Pour plus d'informations, on pourra se référer au site www.vega.com. VEGA lineas de productos están protegidas por los derechos en el campo de la propiedad indus- trial. Para mayor información revise la pagina web www.vega.com.
  • Page 58 Source holder 9 Handling permit 10 HART 32 Time 31 Heat 16 Type label 7 Installation position 13 Unit 26 Instrument features 33 Instrument return form 42 Isotope Voltage supply 17, 47 – Co-60 25 POINTRAC 31 • Foundation Fieldbus...
  • Page 59 INDEX Water cooling 16 POINTRAC 31 • Foundation Fieldbus...
  • Page 60 Subject to change without prior notice © VEGA Grieshaber KG, Schiltach/Germany 2016 VEGA Grieshaber KG Phone +49 7836 50-0 Am Hohenstein 113...