Floating-point Math Instructions

5-21-18 EXPONENT: EXP(467)

Ladder Symbol
(467)
EXP
S
Variations
↑EXP(467)
Description
Relation Between Input Data and Result
Precautions
Flags
Operand Data Areas
S: First source word
R
R: First result word
When the execution condition OFF, EXP(467) is not executed. When the execu-
tion condition is ON, EXP(467) computes the exponent for the 32-floating-point
content of S and S+1, and places the result in R and R+1. The operation is
executed with 2.718282 taken as the base (e).
S+1
e
R+1
If the absolute value of the result is greater than the maximum value that can be
expressed for floating-point data, the Overflow Flag (A50009) will turn ON and
the result will be output as ±R.
If the absolute value of the result is less than the minimum value that can be ex-
pressed for floating-point data, the Underflow Flag (A50010) will turn ON and the
result will be output as 0.
S and S+1must be floating-point data.
Note Refer to page 101 for general precautions on operand data areas.
ER (A50003):
S and S+1is not floating-point data.
The content of a*DM word is not BCD when set for BCD.
EQ (A50006):
The exponent and mantissa of the result are 0.
N (A50008):
OFF when the computation is executed.
OF (A50009):
The absolute value of the result is greater than the maximum
value that can be expressed for floating-point data.
UF (A50010):
Absolute value of the result is less than the minimum value
that can be expressed for floating-point data.
CIO, G, A, T, C, #, DM
CIO, G, A, DM
Source (floating-point data, 32 bits)
S
Result (exponent, floating-point data, 32 bits)
R
R
Section 5-21
S: Input data
R: Result