Configuring And Installing Modules; Dc Power Supply Wiring Instructions - IMC Networks IE-MediaChassis/1-DC Operation Manual

Imc networks ie-mediachassis/1-dc media converters: install guide
Hide thumbs Also See for IE-MediaChassis/1-DC:
Table of Contents

Advertisement

Configuring and Installing Modules

IMC Networks recommends disconnecting the chassis power before proceeding.
1.
To install an iMcV module, slide the module into the chassis until the
module is firmly seated in the backplane.
2.
Secure the module to the chassis by tightening the captive thumb screw on
the iMcV module.
3.
Attach the network cables between the iMcV module and other devices that
will be interconnected.
4.
Connect the DC power source.

DC Power Supply Wiring Instructions

The following image shows the wiring configuration for a 48 VDC power supply in a
negative ground system application. For positive ground system applications remove
the chassis ground shorting jumper and connect it between the positive terminal and
the chassis ground terminal. Alternatively, the chassis grounding jumper can be
eliminated and the chassis ground connected at the power source.
Incorrect wiring will result in chassis malfunction. The IE-MediaChassis/1-DC is
compliant with Isolated Grounding Plane practices. The POSITIVE and NEGATIVE
terminals are isolated from chassis ground and must have a ground reference at
the power-sourcing equipment.