2.0 - Installation

2.1 - Mechanical Installation

The DCY-2058 and 2059 Stations front panels have 1/8DIN size (48 x 96mm).
They are fixed by the rails which press them against the back side of the panel.
After preparing a 45 x 92mm cut in the panel, remove the rails from the Station
and slide its rear through the cut until its front reaches the panel. Place the rails again in
the Station from the back of the panel and tighten the screws as shown in figure 2.
Fig. 2 - Dimensional drawing, panel mounting cutout and side view

2.2 - Electrical Installation

The DCY-2058 and 2059 Auto-Manual / Auto / Manual Stations may be powered
by voltage between 90 and 240VAC or 130 to 340VDC (any polarity); 24VDC, 12VDC
(for other models). Remember that the internal circuit is powered whenever the
instrument is connected to the external power supply.