Calibration of voltage input (0 to 5V)
In order to calibrate the voltage input (0 to 5V) connect an accurate DC voltage
source to the channel to be calibrated (terminals 2(+) and 3(-) for channel 1 or 5(+) and
6(-) for channel 2). The two voltage references listed on table 4 will be required.
Calibration of voltage input (0 to 10V)
In order to calibrate the voltage input (0 to 10V) connect an accurate DC
voltage source to the channel to be calibrated (terminals 1(+) and 3(-) for channel 1
or 4(+) and 6(-) for channel 2). The two voltage references listed on table 5 will be
required.
Calibration of current input (0 to 20mA)
In order to calibrate the current input (0 to 20mA) connect an accurate DC current
source to the channel to be calibrated (terminals 1(+) and 3(-) for channel 1 or 4(+) and
6(-) for channel 2). The two current references listed on table 6 will be required.
Reference
0.0000V
5.0000V
Table 4 - Required voltages for the calibration
of voltage inputs from 0 to 5V
Reference
0.0000V
10.0000V
Table 5 - Required voltages for the calibration
of voltage inputs from 0 to 10V
Reference
0.000 mA
20.000 mA
Table 6 - Required current for the calibration
of current inputs from 0 to 20mA
DCY-2058 and DCY-2059
Mnemonic
0V
5V
Mnemonic
0V
10V
Mnemonic
0mA
20mA
Maintenance