Voltage Input - Presys DCY-2058 Technical Manual

Auto-manual / auto / manual stations
Table of Contents

Advertisement

PRESYS
⏐ Instruments
DCY-2058 and DCY-2059

2.3.2 - Voltage Input

0 to 5VDC voltage must be applied between terminals 2(+) and 3(-) in case of
input 1 and between terminals 5(+) and 6(-) in case of input 2. 0 to 10VDC voltage must
be applied between terminals 1(+) and 3(-) in case of input 1 and between terminals 4(+)
and 6(-) in case of input 2. Those connections are illustrated in figure 5.
Fig. 5 - Voltage Source Connection