A minimum circuit breaker to use for this system is a 20A, D-curve (note, a 20A C-curve breaker will not
discriminate with the rectifier fuse). Therefore, when used with the 2.5mm
breaker should be used.
Alternatively, a 32A C-curve breaker, or greater, can be used. However, AC cable provided may have to
be replaced for a larger cable
If a fuse is used upstream, then any BS88 or NH g style fuse, of 20A or greater rating will discriminate.
6.5.

DC Cabling

CAUTION:
Use extreme care when fitting batteries & their connections. Remove all jewelry
and rings from oneself prior to commencing the installation. Always use insulated tools when fitting
batteries and take extreme care not to short terminals when working on them.

6.5.1. Terminal Block Labeling

Note: Your Centurion II Load & Battery Terminal Blocks maybe labeled differently than shown in photos
on the following page. Some Centurion II shelves' terminal blocks are identified by Numbers which are
the Live or Hot terminals and the words Batt. Common or Load Common which are the Return or
Ground terminals – see polarity table below.
System Voltage
-48 VDC
+24 VDC

6.5.2. Terminal Block Max Wire Size/Recommended Torque Specification

Connection
AC Input
AC Earth
Loads 1 – 8
Loads 9 - 16
Note: A larger breaker may be used even though in theory it may appear that the 2.5mm wire is not
fully protected. In fact, it is protected on two accounts. Firstly, it is protected by the rectifier input
fuse (which is only a short distance away). Secondly, the rectifiers are power limited on their input.
Therefore, they can never be overloaded. As a result, the wire can never be over-loaded by the
rectifier – it can only see fault current. As a result, depending on local authorities, only fault current
protection may be catered for by the upstream protective device.
1
.
"Numbered' (AKA: Live or Hot)
Max AWG
Newmar • 1580 Sunflower Ave, Suite 100, Costa Mesa, CA 92626
Phone: 714-751-0488 • E-mail: techservice@Newmarpower.com
cable supplied, a 20A, D-curve
2
'Common' (AKA: Return or Ground)
-
+
8
2
8
10
9
+
-
Recommended Torque
10.5 in/Lbs.
22 in/Lbs.
10.5 in/Lbs.
10.5 in/Lbs.