Measuring voltage on output: Load circuit breakers are off but I'm measuring DC voltage on the
output terminal block.
This is normal. The load breakers are monitored electronically via a diode to a digital input
on the EM4x. This is a high impedance residual voltage and does not present a hazard to
the
AC Meter Shows Incorrect Voltage
Meter requires greater than a 2-amp load to measure correctly
EM4x Module does not stay in place
On the left side of the module is a small ball screw that can be adjusted to maintain
proper holding force of the EM4x inside the chaise.
Rectifiers come out of shelf
Verify that the rectifier is fully inserted and using a small flathead screwdriver the green locking tab
on the right side is pressed down.
No output from rectifiers
Verify correct AC input voltage:
Confirm operation voltages between each set of Line inputs A, B, and C:
A-L1 to A-L2 = 208 or 230 volts, B-L1 to B-L2 = 208 or 230 volts, C-L1 to C-L2 = 208 or 230
volts
Check voltages between each set of Line inputs and ground:
A-L1 to Ground = 208 or 230 volts, B-L1 to Ground = 208 or 230 volts, C-L1 to Ground = 208
or 230 volts
A-L2 to Ground = 208 or 230 volts, B-L2 to Ground = 208 or 230 volts, C-L2 to Ground = 208
or 230 volts