Dc Cabling; 4.3.1 Terminal Block Labeling; Terminal Block Max Wire Size/Recommended Torque - NewMar Centurion II Power System Installation & Operation Manual

Dc power system -48 vdc and +24 vdc
Hide thumbs Also See for Centurion II Power System:
Table of Contents

Advertisement

 
 
 
 
 
 
Alternatively, a 32A C-curve breaker, or greater, can be used. However, AC cable provided
may have to be replaced for a larger cable
If a fuse is used upstream, then any BS88 or NH g style fuse, of 20A or greater rating will
discriminate.
 
 
4.3

DC Cabling

Use extreme care when fitting batteries & their connections. Remove all jewelry
CAUTION:
and rings from oneself prior to commencing the installation. Always use insulated
tools when fitting batteries and take extreme care not to short terminals when
working on them.
 
 

4.3.1 Terminal Block Labeling

Note: Your Centurion II Load & Battery Terminal Blocks maybe labeled differently than shown in
photos on the following page. Some Centurion II shelves' terminal blocks are identified by
Numbers which are the Live or Hot terminals and the words Batt. Common or Load Common
which are the Return or Ground terminals – see polarity table below.
 
 
System Voltage
-48 VDC
+24 VDC
 
4.3.2 Terminal Block Max Wire Size/Recommended Torque Specification 
 
Connection
AC Input
AC Earth
Loads 1 – 8
Loads 9 - 16
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
1
NOTE: 
A larger breaker may be used even though in theory it may appear that the 2.5mm
it is protected on two accounts.  Firstly it is protected by the rectifier input fuse (which is only a short distance away).  Secondly, 
the rectifiers are power‐limited on their input.  Therefore, they can never be overloaded.  As a result, the wire can never be 
over‐loaded by the rectifier – it can only see fault current.  As a result, depending on local authorities, only fault current 
protection may be catered for by the upstream protective device. 
 
• Phone: 714-751-0488 • E-mail: techservice@newmarpower.com
1
.
"Numbered' (AKA: Live or Hot)
-
+
Max AWG
8
2
8
10
Newmar • PO Box 1306, Newport Beach, CA 92663
'Common' (AKA: Return or Ground)
+
-
Recommended Torque
10.5 in/Lbs.
22 in/Lbs.
10.5 in/Lbs.
10.5 in/Lbs.
wire is not fully protected.  In fact 