6.1 Description

These addressable modules monitor conventional contact-type alarm initiating devices. You can configure module circuits as NFPA
Style B (Class B) or Style D (Class A) Initiating Device Circuits (IDC). There is no limit to the number of contact-type devices installed
on a monitor module IDC.
For more information on the individual module specifications refer to the Installation Instructions that are provided with this device. For
information on transponders, refer to the specific transponder manual.
6.1.1 Addressable Monitor Module
The FMM-1 is an addressable module that monitors either a Style B (Class B) or Style D (Class A) IDC of dry-contact input devices.
This module is capable of participating in degraded mode where supported by the FACP.
6.1.2 Zone Interface Module
The FZM-1 is similar to the FMM-1, except it is used to monitor compatible two-wire, 24 volt, conventional (non-addressable) smoke
detectors on a Style B (Class B) or Style D (Class A) IDC.
Notifier SLC Wiring Manual — P/N 51253:U5 12/20/2017

Section 6: Monitor Modules

IDC Return –
IDC Return +
Areas used to record the device
address and SLC number.
IDC Return –
IDC Return +
Areas used to record the device
address and SLC number.
Figure 6.2 FZM-1 Zone Interface Module
IDC Out +
IDC Out –
Figure 6.1 FMM-1 Monitor Module
24 VDC –
24 VDC +
IDC Out +
IDC Out –
SLC–
Rotary
SLC+
Switches
SLC–
Rotary
SLC+
Switches
33