Monitor Modules

6.6 NFPA Style D IDC Using Zone Interface Modules

Connect the SLC wiring to the module terminals 1 (–) and 2 (+).
Each FZM-1 module takes one address on the SLC. Use the rotary switches on the module to set it to the required SLC address.
Figure 6.9 shows typical wiring for a supervised and power-limited NFPA Style D (Class A) IDC using the FZM-1 module.
Module installation notes:
1.
The Initiating Device Circuit (IDC) is supervised and current-limited to 210 microamps @ 24 VDC (nominal).
2.
The IDC provides the following services (do not mix):
• Fire alarm service
• Automatic and manual waterflow alarm service with normally open contact devices
• Sprinkler supervisory service with normally open contact devices
• Security service
3.
Refer to the Device Compatibility Document for compatible smoke detectors.
38
Two-wire
smoke
detectors
3.9K ELR
(supplied with module)
IDC
Figure 6.8 Typical Style B IDC Wiring with FZM-1
NFPA Style D IDC Using Zone Interface Modules
24 VDC Resettable power.
90 mA External 24 volt supply
required. (Non-resettable power
may be used for NFS-320, NFS-
320SYS, NFS2-640/E, NFS-640,
NFS2-3030, or NFS-3030 when
operating in FlashScan mode.)
FZM-1
Notifier SLC Wiring Manual — P/N 51253:U5 12/20/2017
SLC