Honeywell Notifier AFP-100 Wiring Manual page 75

Intelligent control panel slc
Table of Contents

Advertisement

UL-listed SLC Device
FTM-1
Fault Isolator Module
ISO-X
Multi-input/output modules
FDRM-1
XP6-C
XP6-R
XP10-M
XP6-MA
Notifier SLC Wiring Manual — P/N 51253:U5 12/20/2017
ULC-listed SLC Device
FTM-1A
ISO-XA
FDRM-1A
XP6-CA
XP6-RA
XP10-MA
XP6-MAA
Firefighter's Telephone Module; FlashScan-only device for use with Fire
Fighters Telephone.
The Fault Isolator Module protects the system against wire-to-wire short
circuits on the SLC. It should be placed between groups of sensors in a
Style 6 or Style 7 SLC to isolate short- and open-circuit problems and protect
the rest of the loop so it can continue to operate normally. It is not
addressable, but listed here due to its use in an SLC.
Dual Class B monitor / Form-C relay module.
Controls six NAC or speaker/telephone circuits. (Not listed for use in
releasing applications.)
Controls six Form-C relays.
Supervises ten Class-B addressable Initiating Device Circuits (IDC) which
monitor normally open contact initiating devices.
Monitors six zones of conventional two-wire detectors.
Canadian Versions of SLC Devices
Description
75