NFPA Style D IDC Using Zone Interface Modules
Notifier SLC Wiring Manual — P/N 51253:U5 12/20/2017
90 mA External 24 volt supply required
Two-wire
smoke
NFS2-640, NFS-640, NFS2-3030, or
detectors
IDC
3.9K ELR
(supplied with module)
Figure 6.9 Typical Style D IDC Wiring with FZM-1
24 VDC Resettable power.
(Non-resettable power may be used
for NFS-320, NFS-320SYS,
NFS-3030 when operating in
FlashScan mode.)