Nfpa Style 6 Slc - Honeywell Notifier AFP-100 Wiring Manual

Intelligent control panel slc
Table of Contents

Advertisement

NFPA Style 6 SLC

4.3 NFPA Style 6 SLC
NFPA Style 6 requirements can be met by using the diagram below.
B+ B–
Notifier SLC Wiring Manual — P/N 51253:U5 12/20/2017
SLC Out
SLC Return
A– A+
Control Panel
SLC
Figure 4.2 Basic NFPA Style 6 SLC
NOTE: T-tapping of the SLC wiring is NOT allowed for Style 6 configuration.
Two-wire Addressable Detector
Addressable Module
SLC Circuits without Isolators
25