Model 3144P
Installation in
Conjunction with a
Model 333 HART
Tri-Loop
Figure 2-8. HART Tri-Loop
Installation Flowchart.
No
Install the
Model 3144P
2-10
Use the dual-sensor option Model 3144P transmitter that is operating with two
sensors in conjunction with a Model 333 HART Tri-Loop
Signal Converter to acquire an independent 4–20 mA analog output signal for
each sensor input. During normal operation, the Model 3144P transmitter with
dual-sensor option outputs four out of the six following digital process
variables: sensor 1, sensor 2, differential temperature, average temperature,
first good temperature, and transmitter terminal temperature. The HART
Tri-Loop divides the digital signal and outputs any or all of these variables into
as many as three separate 4–20 mA analog channels.
Refer to Figure 2-8 for basic installation information. Refer to the Model 333
HART Tri-Loop HART-to-Analog Signal Converter Reference Manual
(document number 00809-0100-4754) for complete installation information.
START
HERE
Unpack the
Tri-Loop
Review the
Tri-Loop
Reference
Manual
Model 3144P
Installed?
Yes
Set the Model
3144P Burst
Command
Order
Set the Model
3144P to Burst
HART
Command 3
INSTALL THE
TRI-LOOP
Review
Tri-Loop
Installation
Considerations
Mount the
Tri-Loop to a
DIN Rail
Run Wires from
Model 3144P to
Burst Input
Terminals
Install Channel
1 Wires from
Tri-Loop to
Control Room
OPTIONAL:
Install Channel
2 Wires from
Tri-Loop to
Control Room
OPTIONAL:
Install Channel
3 Wires from
Tri-Loop to
Control Room
Reference Manual
00809-0100-4021, Rev AA
®
HART-to-Analog
COMMISSION
THE TRI-LOOP
Configure the
Tri-Loop to
Receive Model
3144P Burst
Commands
No
Pass System
Test?
Yes
DONE
March 2002
Refer to the
HART Tri-Loop
Reference
Manual