Using The Transmitter With The Hart Tri-Loop - Emerson Rosemount 644 Reference Manual

Temperature transmitter
Hide thumbs Also See for Rosemount 644:
Table of Contents

Advertisement

Reference Manual
00809-0200-4728
Change transmitter address using a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Change transmitter address using AMS Device Manager
Procedure
1. Right click on the device and select Configuration Properties from the menu.
2. In HART Revision 5 mode:
3. In HART Revision 7 mode:
2.13

Using the transmitter with the HART Tri-Loop

To prepare the transmitter with dual-sensor option for use with a Rosemount 333 HART
Tri-Loop, the transmitter must be configured to Burst Mode and the process variable
output order must be set. In Burst Mode, the transmitter provides digital information for
the four process variables to the HART Tri-Loop. The HART Tri-Loop divides the signal into
separate 4–20 mA loops for up to three of the following choices:
Primary Variable (PV)
Secondary Variable (SV)
Tertiary Variable (TV)
Quaternary Variable (QV)
When using the transmitter with dual-sensor option in conjunction with the HART Tri-
Loop, consider the configuration of the differential, average, first good temperatures,
Sensor Drift Alert, and Hot Backup features (if applicable).
Note
The procedures are to be used when the sensors and transmitters are connected,
powered, and functioning properly. Also, Field Communicator must be connected and
communicating to the transmitter control loop. For communicator usage instructions, see
Verify configuration using the Field
Emerson.com/Rosemount
a) In the HART tab, enter poll address into the Polling Address box, select
Apply.
a) In the HART tab, select the Change Polling Address button.
Communicator.
Configuration
March 2021
1, 2, 1
®
51

Advertisement

Table of Contents
loading

Table of Contents