Daikin VRV RXYMQ-A Series Service Manual page 107

R-410a heat pump 50/60 hz
Table of Contents

Advertisement

SiME332106E
1.4.22 Ceiling Height Setting, Setting of Normal Airflow
Make the following setting according to the ceiling height.
 FXFSQ25-80AR
Mode
 FXFSQ100-140AR
Mode
Note(s)
1. The Second Code No. is factory set to Standard/All-direction airflow. For High ceiling (1) or
2. A closing member kit (optional) is required for 4-, 3-, or 2-direction airflow.
 FXFSQ-AR with Designer panel
Mode
FXAQ-AR
Mode
1.4.23 Airflow Direction Setting
Set the airflow direction of indoor units as given in the table below. (Set when sealing material
kit of air discharge outlet has been installed.) The second code No. is factory set to 01.
13 (23)
Part 5 Field Settings and Test Operation
First
Second
Code
Code
No.
No.
No.
01
13
0
02
(23)
03
Higher Ceiling
First
Second
Code
Code
No.
No.
No.
01
13
0
02
(23)
03
Higher Ceiling
(2), initial setting by remote controller is required.
First
Second
Code
No.
Code No.
No.
01
13
0
02
(23)
03
First
Second
Code
No.
Code No.
No.
01
13
0
02
(23)
03
Mode
First
Second
No.
Code No.
Code No.
01
1
02
03
Contents
All round
outlet
Lower than
Standard
2.7 m
Lower than
High Ceiling
3.0 m
Lower than
3.5 m
Contents
All round
outlet
Lower than
Standard
3.2 m
Lower than
High Ceiling
3.6 m
Lower than
4.2 m
FXFSQ25-80AR
Contents
(All round outlet)
Standard
High Ceiling (1)
High Ceiling (2)
Field Settings for Indoor Unit
: Factory setting
Ceiling Height
4-way
3-way
Outlets
Outlets
Lower than
Lower than
3.1 m
3.0 m
Lower than
Lower than
3.4 m
3.3 m
Lower than
Lower than
4.0 m
3.5 m
: Factory setting
Ceiling Height
4-way
3-way
Outlets
Outlets
Lower than
Lower than
3.4 m
3.6 m
Lower than
Lower than
3.9 m
4.0 m
Lower than
Lower than
4.5 m
4.2 m
: Factory setting
FXFSQ100-140AR
(All round outlet)
Lower than
Lower than
2.4 m
Lower than
Lower than
2.7 m
Lower than
Lower than
3.2 m
: Factory setting
Contents
Standard
Slightly higher
High
: Factory setting
Contents
4-way airflow
3-way airflow
2-way airflow
2-way
Outlets
Lower than
3.5 m
Lower than
3.8 m
2-way
Outlets
Lower than
4.2 m
Lower than
4.2 m
3.2 m
3.6 m
4.2 m
101