Troubleshooting by Error Code
Note(s)
1. Error codes and thermistors
Reference
CHECK 11 Refer to page 281.
216
Error
Applicable Thermistor
Code
H9
Outdoor air thermistor
J3
Discharge pipe thermistor
J5
Suction pipe thermistor
J6
Heat exchanger deicer thermistor
J7
Subcooling heat exchanger liquid pipe thermistor
J8
Heat exchanger liquid pipe thermistor
J9
Subcooling heat exchanger gas pipe thermistor
SiME332106E
RXYMQ-A
Electric symbol
Connector
R1T
X18A
R21T
X19A
R3T
R7T
X30A (Group
R5T
connector)
R4T
R6T
Part 6 Service Diagnosis