Normal Control
5.5
Electronic Expansion Valve Control
Electronic expansion valve Y1E
Cooling: electronic expansion valve is used only at fully closed or fully open condition:
Heating: electronic expansion valve is used in PID control suction superheat:
5.6
Step Control of Outdoor Fans
Used to control the revolutions of outdoor fans in the steps listed in table below, according to
condition changes.
* When the system detects that outdoor air temperature (Ta) reaches 41°C or more, the control
of fan revolutions will be changed to 1,060 rpm automatically.
Note(s)
Table shown above is for external static pressure level 0. In case of high external static
When capacity priority mode is set, values may differ.
58
Compressor(s) OFF: fully closed (0 pulse).
Compressor ON:
Fully open (480 pulses)
Normally, the control is used to reduce the PCB temperature.
Compressor
0 Hz
Main
480
Y1E
pulses
0
Compressor(s) OFF: fully closed (0 pulse).
Compressor ON:
At startup: closed (check suction pressure drops)
Modulated opening by:
- Suction superheat = accumulator inlet °C – evaporating temperature.
- Discharge superheat = discharge compressor °C – condensing temperature.
- Preventive change when compressor capacity step changes.
- Limited opening when condensing temperate exceeds target condensing.
Compressor
0 Hz
Main
480
Y1E
pulses
0
Step No.
RXYMQ4AVMK
Cooling
0
0
1
200
2
250
3
300
4
360
5
420
6
490
7Y
560
7X
630
8
700
pressure, the unit will re-adjust fan revolutions automatically and values may differ.
Fan revolutions (rpm)
Heating
Cooling
0
0
200
440
250
440
300
440
370
440
440
480
515
550
590
650
670
830
750
960*
SiME332106E
RXYMQ4-6AYFK
Heating
0
440
440
440
440
550
660
780
940
1,060
Part 4 Functions and Control