Daikin VRV RXYMQ-A Series Service Manual page 179

R-410a heat pump 50/60 hz
Table of Contents

Advertisement

SiME332106E
5.8.2 Power Supply Voltage Abnormality (FXFSQ-AR)
Applicable
FXFSQ-AR
Models
A8-01
Error Code
Method of Error
This error is detected by checking the voltage status with the microcomputer.
Detection
Error Decision
Overvoltage or voltage drop is detected on the fan driver.
Conditions
Supposed
 Defective connection of power supply connector
Causes
 Defective indoor unit PCB (A1P)
 External factors (e.g. noise)