Power Supply Voltage Imbalance - Daikin VRV RXYMQ-A Series Service Manual

R-410a heat pump 50/60 hz
Table of Contents

Advertisement

Troubleshooting by Error Code

5.48 Power Supply Voltage Imbalance

Applicable
RXYMQ4-6AYFK
Models
P1
Error Code
Method of Error
Detect voltage imbalance through inverter PCB.
Detection
Error Decision
Power supply voltage imbalance exceeds approximately 12 V.
Conditions
Error is not decided while the unit operation is continued.
P1 will be displayed by pressing the inspection button.
Supposed
 Open phase
Causes
 Interphase voltage imbalance
 Defective capacitor in the main circuit
 Defective inverter PCB
 Defective wiring in the main circuit
234
SiME332106E
Part 6 Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents