Outdoor Unit Main Pcb Abnormality - Daikin VRV RXYMQ-A Series Service Manual

R-410a heat pump 50/60 hz
Table of Contents

Advertisement

Troubleshooting by Error Code

5.22 Outdoor Unit Main PCB Abnormality

Applicable
All outdoor unit models
Models
E1
Error Code
Method of Error
Abnormality is detected under the communication conditions in the hardware section between
Detection
the indoor unit and outdoor unit.
Error Decision
When the communication conditions in the hardware section between the indoor unit and the
Conditions
outdoor unit are not normal.
Supposed
 Defective outdoor unit main PCB
 Disconnection of the inside/outside relay wires
Causes
Troubleshooting
194
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Turn OFF the power once and
turn ON again.
Return to normal?
NO
Check if
inside / outside
YES
relay wires of outdoor
unit main PCB is
disconnected.
NO
YES
SiME332106E
External factor other than
error (for example, noise
etc.).
Connect the inside/outside
relay wires correctly.
Replace the outdoor unit
main PCB (A1P).
Part 6 Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents