ComAp InteliDrive FLX LITE Manual page 152

Engine controller for pumps and compressors
Table of Contents

Advertisement

AIN6 Eval
Setpoint group
Engine protection
Range [units]
NORMAL, CLASS C [-]
Default value
NORMAL
Step
-
Comm object
13076
Description
Protection behaves according to the standard configuration of Wrn/Sd alarm in
NORMAL
LiteEdit AINx configuration screen. Default state.
The protection is type "Running only" and does not depend on Running only tick in
LiteEdit AINx Alarm properties configuration window. Protection (Class C) is
CLASS C
working after AINx Del or sooner when appropriate value increases over AINx Wrn
limit +3 seconds - after engine start. Warning/ShutdDown protection is activated
with fix delay 0.5 s.
Note: Class C protection is working and corresponding setpoints are visible only when corresponding
AIN is configured in Modify->Alarm properties-> Direction-> Window prot.
6 back to List of setpoints
AIN6 LowWrn
Setpoint group
Engine protection
Range [units]
0 .. 10000 [U12]
Default value
20
Step
1
Comm object
13359
Description
Low Warning limit level for AIN6.
6 back to List of setpoints
AIN6 LowSd
Setpoint group
Engine protection
Range [units]
0 ... 10000 [U12]
Default value
10
Step
1
Comm object
13360
Description
Low ShutDown limit level for AIN6.
6 back to List of setpoints
ID-FLX Lite Global Guide
Related FW
2.5.0
-
Related applications
Related FW
2.5.0
-
Related applications
Related FW
2.5.0
-
Related applications
152