ComAp InteliDrive FLX LITE Manual page 105

Engine controller for pumps and compressors
Table of Contents

Advertisement

RunHoursSource
Setpoint group
Basic settings
Range [units]
[ECU, INTERNAL, AUTO]
Default value
Step
-
Comm object
13345
Description
This setpoint is used for adjustment of RunHours source of the engine.
ECU
RunHours are all the time read from ECU.
INTERNAL
RunHours are counted from the inner counter of the controller.
If is coming from ECU rational value higher than 0, then the RunHours are taken from
AUTO
ECU, in second case are displayed internal hours from controller. Default state.
IMPORTANT: Some types of ECUs reset RunHours counter to 0, if the supply was
disconnected.
6 back to List of setpoints
Main Screen
Setpoint group
Basic settings
Range [units]
[SHOW TIMERS, SHOW AIN]
Default value
Step
-
Comm object
13346
Description
Change the display of the main Measurment screen.
SHOW TIMERS Standard display with timers on the left side of the screen. Default state.
Instead of timers are on the left side of the screen displayed values of analog inputs AIN6
SHOW AIN
and AIN7.
6 back to List of setpoints
ID-FLX Lite Global Guide
Related FW
2.5.0
-
Related applications
Related FW
2.5.0
-
Related applications
105