Huawei SmartLogger2000-10-C-JP Quick Manual page 3

Table of Contents

Advertisement

No.
Port (Silk Screen)
9
Default
10
AC1, AC2
11
12
AI1–AI7
13
PT1, PT2
14
AO1–AO4
15
DI1–DI8
Note a: Passive means that the AI port can connect to a sensor that needs to be energized separately.
2
Typical Cable Connection Scenarios
2.1
Non-Smart Array Controller Scenario
1. The SmartLogger can connect to an inverter over an RS485 communications cable.
2. The power cable delivered with the SmartLogger is 1 meter long, the power adapter cable is 1.5
meters long, the network cable is 2.2 meters long, and the AC power cable is 1.5 meters long.
Reserve the installation positions for components based on the cable lengths.
3. The tables under figures list only the components to be configured by the customer in the
corresponding scenario.
Optical Fiber
Function
Resets and restarts the Bluetooth module or resets
the SmartLogger IP address to the default IP address
Default key
(valid within 5 minutes). The default IP address is
192.168.0.10.
Connects to three-phase (U, V, and W) inputs, and is
AC power cable
used for PLC (MBUS) with the SUN2000 over AC
ports
power cables. If PLC (MBUS) function is not used,
you do not have to connect cables to these ports.
Shell ground point
N/A
AI1 supports 0–10 V input voltage (passive
Analog input
AI7 support 0–20 mA and 4–20 mA input current
(passive).
Analog input
Analog output (AO) 4–20 mA and 0–20 mA output current
Connects to a dry contact input. GND1 and GND2
Digital input (DI)
are ground ports for DI signals.
Description
PT1 supports the connection to a three-wire or two-
wire PT100/PT1000 temperature sensor.
PT2 supports the connection to only a two-wire
PT100/PT1000 temperature sensor.
2