6
Connecting a Cable to the DI Port
1. The SmartLogger provides eight DI ports, namely, DI1(GND1) to DI4(GND1) and DI5(GND2) to
DI8(GND2). An OVGR can connect to any DI port.
2. Two-core or multiple-core cables with a cross sectional area of 1.5 mm
1. Prepare a cable with an appropriate length,
strip a part of the insulation layer, and
connect the stripped cable core to the
OVGR.
2. Strip 8 mm of the insulation layer at the
other end.
3. Remove the terminal block from the
SmartLogger DI port.
NOTE
Remove the terminal block
using a flat-head screwdriver.
No.
Port
Dry contact input common terminal
1
GND1
1, used for active power derating
for DI1–DI4
2
DI1
DI_1
3
DI2
DI_2
4
DI3
DI_3
5
DI4
DI_4
6
DI5
DI_5
7
DI6
DI_6
8
DI7
DI_7
9
DI8
DI_8
Dry contact input common terminal
2, used for reactive power
10
GND2
compensation for DI5–DI8
4. Connect the stripped cable core to the terminal
block of the DI port on the SmartLogger.
5. Insert the terminal block into the SmartLogger
DI port.