FUNCTIONS AND FEATURES
1.Parallel operation
2.Series operation
3.Daisy chain
4.Constant power control
5.Output resistance control
6.Slew rate control
7.Arbitrary waveforms
PROGRAMMING AND READBACK (USB, LAN, RS232/485, Optional IEEE (*16) Interface)
1.Vout programming accuracy (*15)
2.Iout programming accuracy (*14)
3.Vout programming resolution
4.Iout programming resolution
5.Vout readback accuracy
6.Iout readback accuracy (*14)
7.Vout readback resolution
8.Iout readback resolution
PROTECTIVE FUNCTIONS
1.Foldback protection
2.Over-voltage protection (OVP)
3.Over -voltage programming range
4.Over-voltage programming accuracy
5.Output under voltage limit (UVL)
6.Over temperature protection
7.Output under voltage protection (UVP)
FRONT PANEL
1.Control functions
2.Display
3.Front Panel Buttons Indications
4.Front Panel Display Indications
ENVIRONMENTAL CONDITIONS
1.Operating temperature
2.Storage temperature
3.Operating humidity
4.Storage humidity
5.Altitude
MECHANICAL
1.Cooling
2.Weight
3.Dimensions (WxHxD)
4.Vibration
5.Shock
---
Possible. Up to 4 identical units in Master/Slave mode. Refer to instruction manual.
---
Possible. Two identical units. Refer to instruction manual.
---
Power supplies can be connected in Daisy chain to synchronize their turn-on and turn-off.
Limits the output power to a programmed value. Programming via the communication ports or the front
---
panel.
Emulates series resistance. Resistance range: 1~1000mΩ. Programming via the communication ports or
---
the front panel.
Programmable Output rise and Output fall slew rate.
Programming range: 0.0001~999.99 V/mS. or A/mS.
---
Programming via communication ports or front panel.
Profiles of up to 100 steps can be stored in 4 memory cells.
---
Activation by command via communication ports or front panel.
V
10
20
30
---
0.05% of rated output voltage
---
0.1% of actual output current+0.2% of rated output current
---
0.002% of rated output voltage
---
0.0025% of rated output current
---
0.05% of rated output voltage
---
0.2% of rated output current
% of rated
0.011%
0.006%
0.004%
output
voltage
% of rated
output
0.01%
0.002%
0.003%
current
V
10
20
30
Output shut-down when power supply changes mode from CV or Power Limit to CC mode or from CC or
---
Power Limit to CV mode. User presetable. Reset by AC input recycle in autostart mode, by Power
Switch, by OUTPUT button, by rear panel or by communication.
Output shut-down. Reset by AC input recycle in autostart mode, by Power Switchm, by OUTPUT button,
---
by rear panel or by communication.
V
0.5~12
1~24
2~36
+/-1% of rated output voltage
---
Prevents from adjusting Vout below limit. Does not apply in analog programming.
---
Preset by front panel or communication port.
---
Shuts down the output. Auto recovery by autostart mode.
Prevents adjustment of Vout below limit. P.S output turns Off during under voltage condition.
---
Reset by AC input recycle in autostart mode, by Power Switch, by OUTPUT button, by rear panel or by
communication.
---
Multiple options with 2 Encoders.
---
Vout/Iout/Power Limit manual adjust.
---
OVP/UVL/UVP manual adjust.
---
Protection Functions - OVP, UVL, UVP, Foldback, OCL, ENA, ILC.
---
Communication Functions - Selection of LAN, RS232, RS485, USB or Optional communication interface.
---
Output ON/OFF. Front Panel Lock.
---
Communication Functions - Selection of Baud Rate, Address, IP and communication language.
---
Analog Control Functions - Selection Voltage/resistive programming 5V/10V, 5KΩ/10KΩ programming.
---
Analog Monitor Functions - Selection of Voltage/Current Monitoring 5V/10V.
---
Vout: 4 digits, accuracy: 0.05% of rated output voltage +/-1 count.
---
Iout: 4 digits, accuracy: 0.2% of rated output current +/-1 count.
OUTPUT ON, ALARM, PREVIEW, FINE, COMMUNICATION, PROTECTION, CONFIGURATION,
---
SYSTEM, SEQUENCER.
Voltage, Current, Power, CV, CC, CP, External Voltage, External Current, Address, LFP, Autostart,
---
Safestart, Foldback V/I, Remote (communication), RS/USB/LAN/Optional communication interface,
Trigger, Load/Store Cell.
---
100Vac≤Vin≤265Vac: 0~50
O
-30~85
C.
---
---
20~90% RH (no condensation).
10~95% RH (no condensation).
---
Operating: 10000ft (3000m), output current derating 2%/100m or Ta derating 1
---
above 2000m.
Non-operating: 40000ft (12000m).
---
Forced air cooling by internal fans. Airflow direction: From front panel to power supply rear.
Kg
Less than 3.5Kg.
W: 214, H: 43.6, D: 432 (Without busbars and busbars cover), W: 214, H: 43.6, D: 493 (Including
mm
busbars and busbars cover) (Refer to Outline drawing).
---
MIL-810G, method 514.6, Procedure I, test condition Annex C - 2.1.3.1
---
Less than 20G, half sine, 11mS. Unit is unpacked.
62
40
60
80
100
0.003%
0.002% 0.002%
0.011%
0.003%
0.005% 0.006%
0.007%
40
60
80
100
2~44.1
5~66.15
5~88.2 5~110.25 5~165.37 5~330.75 5~661.5
O
C, 100% load. 85Vac≤Vin<100Vac: 0~45
150
300
600
0.007%
0.004%
0.002%
0.015%
0.003%
0.004%
150
300
600
O
C, 100% load.
O
C/100m