Indoor Unit - Samsung AM080FX A Series Service Manual

System air conditioner outdoor unit
Table of Contents

Advertisement

Product Specifications
2-2 Model names of Indoor/Outdoor Unit (cont.)

2-2-2 Indoor unit

Model
1.5
1.7
Slim 1Way CST
( JSF )
Interior 1Way CST
2Way CST
4Way CST
360 CST
Floor Stand Unit
4Way CST S
( 600 X600 )
Duct S ( Slim )
Duct S ( MSP )
► Make sure to use an indoor unit that is compatible with DVM S.
► Indoor units can be connected within the range indicated in following table.
► If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating capacity of the indoor unit may decrease.
► Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity.
0.5 x ∑ (Outdoor unit capacity) ≤ Total capacity of the connected indoor unit ≤ 1.3 x ∑ (Outdoor unit capacity)
► You can connect maximum 64 indoor units to the outdoor unit.
Maximum quantity of connectable indoor unit is set to 64 since outdoor unit only support up to 64 communication address. Indoor unit address can be assigned from 0~63.
If the indoor unit address was assigned from 64~79, E201 error will occur.
► Maximum 32 Wall-mount type indoor units with EEV (AMSSSFNQDEHS, AMSSSJNVDKHS) can be connected.
Samsung Electronics
2.2
2.8
3.2
3.6
Product Specifications
Capacity ( kW )
4.5
5.6
6.0
7.1
24
Samsung Electronics
8.2
9.0
11.2
12.8
14.0
16.0
25