Error Due To Using Single Type Outdoor Unit In A Module Installation - Samsung AM080FX A Series Service Manual

System air conditioner outdoor unit
Table of Contents

Advertisement

Troubleshooting
4-3 Appropriate Measures for Different Symptom (cont.)

4-3-56 Error due to using single type outdoor unit in a module installation

Outdoor Unit Display
Indoor Unit Display
Judgment Method
• Refer to the judgment method below.
1. Cause of problem
Is outdoor unit single type exclusive
use model (non-modular model)?
Is installed by outdoor unit module?
Outdoor unit single type exclusive use
model (non-modular model), can not be
module installation.
(Single type only installation)
Samsung Electronics
Yes
Is the outdoor unit EEPROM accurately
connected to connector?
Yes
Download relevant model EEPROM and
then reset.
※ Execute automatic commissioning
for "UP" cancellation after EEPROM
download.
-
No
Yes
No
Connect outdoor unit EEPROM
and then reset.