Samsung VRF DVM S Water Technical Data Book
Hide thumbs Also See for VRF DVM S Water:

Advertisement

VRF
Technical
Data Book
DVM S Water for Europe
(R410A, 50/60Hz, HP/HR)
Model : Premium energy efficiency Type
Premium compact type

Advertisement

Table of Contents
loading

Summary of Contents for Samsung VRF DVM S Water

  • Page 1 Technical Data Book DVM S Water for Europe (R410A, 50/60Hz, HP/HR) Model : Premium energy efficiency Type Premium compact type...
  • Page 2 History Version Modification Date Remark Ver. 1.0 Release DVM S Water for Europe TDB '17. 06. 23 Ver. 1.01 Modify the Accessory Compatibility table for MCU kit(P67) '17. 09. 13...
  • Page 3 Nomenclature Outdoor units Model name (1) Classification (5) Feature1 DVM WATER (2) Capacity (6) Feature2 x 1/10 HP (3 digits) Standard + General Temp.+ Module (3) Version (7) Rating Voltage 2013 3Ø, 380~415V, 50/60Hz 2014 3Ø, 380~415V, 50Hz 2015 2016 2017 (8) Mode (4) Product Type...
  • Page 4 30 horsepower (HP) capacity. So instead of installing two 10HP 30HP units you only need one 30HP Samsung unit – using 56% less space 30HP and significantly reducing the costs of valves, fittings and gauges.
  • Page 5: Table Of Contents

    Contents 1. Line-up 2. Specification 3. Electric Characteristics 4. Dimensional Drawing 5. Center of Gravity 6. Electrical Wiring Diagram 7. Sound Level 8. Operating Range 9. Piping Diagram 10. Installation 11. Accessory...
  • Page 6: Line-Up

    1. Line-up 1) Outdoor units combination Table Premium energy efficiency type System Model Capacity (HP) Capa.(HP) Model No. of Modules AM080MXWANR AM100MXWANR AM120MXWANR AM160MXWANR2 AM180MXWANR2 AM200MXWANR AM220MXWANR2 AM240MXWANR2 AM260MXWANR2 AM280MXWANR2 AM300MXWANR2 AM320MXWANR2 AM340MXWANR2 AM360MXWANR2 AM380MXWANR2 AM400MXWANR2 AM420MXWANR2 AM440MXWANR2 AM480MXWANR2 AM500MXWANR2 AM520MXWANR2 AM600MXWANR2...
  • Page 7 1. Line-up 1) Outdoor units combination Table Premium compact type System Model Capacity (HP) Capa.(HP) Model No. of Modules AM300KXWANR AM380MXWANR1 AM400MXWANR1 AM420MXWANR1 AM460MXWANR1 AM480MXWANR1 AM500MXWANR1 AM520MXWANR1 AM540MXWANR1 AM580MXWANR1 AM600MXWANR1 AM620MXWANR1 AM680MXWANR1 AM700MXWANR1 AM800MXWANR1 AM900MXWANR1 NOTE • Make sure to use an indoor unit that is compatible with DVM S WATER-GEO. •...
  • Page 8 1. Line-up 3) Indoor units Capacity (kW) Model Slim 1way cassette (JSF) 2way cassette Global 4way cassette 4way CST (600 X 600) 360 CST Floor Standing Unit Slim duct MSP duct HSP duct Ceiling Console Neo forte Neo forte (with EEV) Hydro unit / HE Hydro unit / HT ERV plus...
  • Page 9 1. Line-up 3) Indoor units Capacity (kW) Model 11.2 12.8 14.0 22.0 28.0 44.8 500CMH 1000CMH Slim 1way cassette(JSF) 2way cassette Global 4way cassette 4way CST (600 X 600) 360 CST Floor Standing Unit Slim duct MSP duct HSP duct Ceiling Console Neo forte...
  • Page 10: Specification

    2. Specification Premium energy efficiency Type Type DVM S Water DVM S Water DVM S Water DVM S Water AM080MXWA∗∗ AM100MXWA∗∗ AM120MXWA∗∗ AM160MXWA∗∗ Outdoor unit module 1 AM080MXWA∗∗ AM100MXWA∗∗ AM120MXWA∗∗ AM080MXWA∗∗ Model Name Outdoor unit module 2 AM080MXWA∗∗ Outdoor unit module 3 Outdoor unit module 4 Power Supply Ø, #, V, Hz...
  • Page 11 2. Specification Premium energy efficiency Type Type DVM S Water DVM S Water DVM S Water DVM S Water AM180MXWA∗∗ AM200MXWA∗∗ AM220MXWA∗∗ AM240MXWA∗∗ Outdoor unit module 1 AM080MXWA∗∗ AM200MXWA∗∗ AM100MXWA∗∗ AM120MXWA∗∗ Model Name Outdoor unit module 2 AM100MXWA∗∗ AM120MXWA∗∗ AM120MXWA∗∗ Outdoor unit module 3 Outdoor unit module 4 Power Supply...
  • Page 12 2. Specification Premium energy efficiency Type Type DVM S Water DVM S Water DVM S Water DVM S Water AM260MXWA∗∗ AM280MXWA∗∗ AM300MXWA∗∗ AM320MXWA∗∗ Outdoor unit module 1 AM080MXWA∗∗ AM080MXWA∗∗ AM100MXWA∗∗ AM120MXWA∗∗ Model Name Outdoor unit module 2 AM080MXWA∗∗ AM200MXWA∗∗ AM200MXWA∗∗ AM200MXWA∗∗...
  • Page 13 2. Specification Premium energy efficiency Type Type DVM S Water DVM S Water DVM S Water DVM S Water AM340MXWA∗∗ AM360MXWA∗∗ AM380MXWA∗∗ AM400MXWA∗∗ Outdoor unit module 1 AM100MXWA∗∗ AM080MXWA∗∗ AM080MXWA∗∗ AM200MXWA∗∗ Model Name Outdoor unit module 2 AM120MXWA∗∗ AM080MXWA∗∗ AM100MXWA∗∗ AM200MXWA∗∗...
  • Page 14 2. Specification Premium energy efficiency Type Type DVM S Water DVM S Water DVM S Water AM420MXWA∗∗ AM440MXWA∗∗ AM480MXWA∗∗ Outdoor unit module 1 AM100MXWA∗∗ AM120MXWA∗∗ AM080MXWA∗∗ Model Name Outdoor unit module 2 AM120MXWA∗∗ AM120MXWA∗∗ AM200MXWA∗∗ Outdoor unit module 3 AM200MXWA∗∗ AM200MXWA∗∗...
  • Page 15 2. Specification Premium energy efficiency Type Type DVM S Water DVM S Water DVM S Water AM500MXWA∗∗ AM520MXWA∗∗ AM600MXWA∗∗ Outdoor unit module 1 AM100MXWA∗∗ AM120MXWA∗∗ AM200MXWA∗∗ Model Name Outdoor unit module 2 AM200MXWA∗∗ AM200MXWA∗∗ AM200MXWA∗∗ Outdoor unit module 3 AM200MXWA∗∗ AM200MXWA∗∗...
  • Page 16 2. Specification Premium compact type Type DVM S Water DVM S Water DVM S Water DVM S Water AM300KXWANR AM380MXWANR1 AM400MXWANR1 AM420MXWANR1 Outdoor unit module 1 AM300KXWANR AM300KXWANR AM300KXWANR AM300KXWANR Model Name Outdoor unit module 2 AM080MXWANR AM100MXWANR AM120MXWANR Outdoor unit module 3 Outdoor unit module 4 Power Supply Ø, #, V, Hz...
  • Page 17 2. Specification Premium compact type Type DVM S Water DVM S Water DVM S Water DVM S Water AM460MXWANR1 AM480MXWANR1 AM500MXWANR1 AM520MXWANR1 Outdoor unit module 1 AM300KXWANR AM300KXWANR AM300KXWANR AM300KXWANR Model Name Outdoor unit module 2 AM080MXWANR AM100MXWANR AM200MXWANR AM120MXWANR Outdoor unit module 3 AM080MXWANR AM080MXWANR...
  • Page 18 2. Specification Premium compact type Type DVM S Water DVM S Water DVM S Water DVM S Water AM540MXWANR1 AM580MXWANR1 AM600MXWANR1 AM620MXWANR1 Outdoor unit module 1 AM300KXWANR AM300KXWANR AM300KXWANR AM300KXWANR Model Name Outdoor unit module 2 AM120MXWANR AM200MXWANR AM300KXWANR AM200MXWANR Outdoor unit module 3 AM120MXWANR AM080MXWANR...
  • Page 19 2. Specification Premium compact type Type DVM S Water DVM S Water DVM S Water DVM S Water AM680MXWANR1 AM700MXWANR1 AM800MXWANR1 AM900MXWANR1 Outdoor unit module 1 AM300KXWANR AM300KXWANR AM300KXWANR AM300KXWANR Model Name Outdoor unit module 2 AM300KXWANR AM300KXWANR AM300KXWANR AM300KXWANR Outdoor unit module 3 AM080MXWANR AM100MXWANR...
  • Page 20 2. Specification NOTE • Specification may be subject to change without prior notice. 1) Cooling capacities are based on; - Indoor temperature : 27°C DB, 19°C WB, Inlet water temperature : 30°C, Equivalent refrigerant piping : 7.5m, Level differences : 0m 2) Heating capacities are based on;...
  • Page 21: Electric Characteristics

    3. Electric Characteristics Single Power Supply Voltage Range Nominal Running Capacity Current [A] Current [A] Model Min. Max. Voltage (-10%) (+10%) Cooling Heating 22.4 AM080MXWANR 50/60 380~415 16.1 28.0 AM100MXWANR 50/60 380~415 16.1 33.6 AM120MXWANR 50/60 380~415 10.3 10.4 20.0 56.0 AM200MXWANR 50/60...
  • Page 22 3. Electric Characteristics Module (Premium compact type) Power Supply Voltage Range Nominal Running Capacity Current [A] Current [A] Model Min. Max. Voltage (-10%) (+10%) Cooling Heating 106.4 AM380MXWANR1 50/60 380~415 32.6 33.1 64.1 112.0 AM400MXWANR1 50/60 380~415 34.5 34.9 64.1 117.6 AM420MXWANR1 50/60...
  • Page 23: Dimensional Drawing

    4. Dimensional Drawing AM080/100/120MXWA∗∗ (8, 10, 12HP) Unit : mm Description Description Name Name 10HP 12HP 10HP 12HP Liquid ref. pipe 9.52 (3/8") 9.52 (3/8") 12.70 (1/2") Water inlet pipe PT 1-1/4 High pressure Communication 15.88 (5/8") 19.05 (3/4") 19.05 (3/4") gas ref.
  • Page 24 4. Dimensional Drawing AM200MXWA∗∗ (20HP) Unit : mm 1100 1098 Name Description Name Description Liquid ref. pipe 15.88 (5/8") Water inlet pipe PT 1-1/4 High pressure gas ref. pipe 28.58 (1 1/8") Communication wiring Low pressure gas ref. pipe 28.58 (1 1/8") External contact wiring Water outlet pipe PT 1-1/4...
  • Page 25 4. Dimensional Drawing AM300KXWA∗∗ (30HP) Unit : mm 1104 Name Description Name Description Liquid ref. pipe Ø 19.05 (3/4") Water inlet pipe Gas ref. pipe Ø 28.58 (1 1/8") Communication wiring High pressure gas ref. pipe Ø 34.92 (1 3/8") External contact wiring Water outlet pipe Power wiring...
  • Page 26: Center Of Gravity

    5. Center of Gravity AM080/100/120MXWA∗∗ (8, 10, 12HP) Unit : mm Model ∗∗ AM080/100/120MXWA...
  • Page 27 5. Center of Gravity AM200MXWA∗∗, AM300KXWA∗∗ (20, 30HP) Unit : mm Model AM200MXWA∗∗ AM300KXWA∗∗...
  • Page 28: Electrical Wiring Diagram

    6. Electrical Wiring Diagram AM080MXWA∗∗~AM200MXWA∗∗ (8~20HP)∗∗ INVERTER PCB1 Printed circuit board (Inverter PBA1) EEV1 Electrical Expansion Valve 1 HOTGAS V/V 1 Solenoid Valve (Hot Gas Bypass1) INVERTER PCB2 Printed circuit board (Inverter PBA2) EEV2 Electrical Expansion Valve 2 HOTGAS V/V 2 Solenoid Valve (Hot Gas Bypass2) EMI PCB1 Printed circuit board (Noise Filter1)
  • Page 29 6. Electrical Wiring Diagram AM300KXWA∗∗ (30HP) INV PBA1 Printed circuit board(Inverter PBA1) EEV1 Electrical Expansion Valve 1 LIQUID(10K) Temp. Sensor (Liquid Tube Temp._10Kohm) INV PBA2 Printed circuit board(Inverter PBA2) EEV2 Electrical Expansion Valve 2 HOTGAS1 V/V Solenoid Valve (Hot Gas Bypass1) EMI PBA1 Printed circuit board(Noise Filter1) EVI-OUT(10K)
  • Page 30: Sound Level

    7. Sound Level Summary Single Capacity Sound Pressure dB(A) Sound Power Model Cooling Heating (dBA) 22.4 AM080MXWANR 28.0 AM100MXWANR 33.6 AM120MXWANR 56.0 AM200MXWANR 84.0 AM300KXWANR Module (Premium energy efficiency type) Capacity Sound Pressure dB(A) Sound Power Model Cooling Heating (dBA) 44.8 AM160MXWANR2 50.4...
  • Page 31 7. Sound Level Summary Module (Premium compact type) Capacity Sound Pressure dB(A) Sound Power Model Cooling Heating (dBA) 106.4 AM380MXWANR1 112.0 AM400MXWANR1 117.6 AM420MXWANR1 128.8 AM460MXWANR1 134.4 AM480MXWANR1 140.0 AM500MXWANR1 145.6 AM520MXWANR1 151.2 AM540MXWANR1 162.4 AM580MXWANR1 168.0 AM600MXWANR1 173.6 AM620MXWANR1 190.4 AM680MXWANR1 196.0...
  • Page 32 7. Sound Data Sound Pressure level Unit: dB(A) Model Cooling AM080MXWA∗∗ AM100MXWA∗∗ AM120MXWA∗∗ AM200MXWA∗∗ AM300KXWA∗∗ NR Curve 1) AM080MXWA∗∗ 2) AM100MXWA∗∗ NR 90 NR 90 NR 85 NR 85 NR 80 NR 80 NR 75 NR 75 NR 70 NR 70 NR 65 NR 65 NR 60...
  • Page 33 7. Sound Data Sound Power Level Unit: dB(A) Model Power AM080MXWA∗∗ AM100MXWA∗∗ AM120MXWA∗∗ AM200MXWA∗∗ AM300KXWA∗∗ 1) AM080MXWA∗∗ 2) AM100MXWA∗∗ NR 70 NR 70 NR 65 NR 65 NR 60 NR 60 NR 55 NR 55 NR 50 NR 50 NR 45 NR 45 NR 40 NR 40...
  • Page 34: Operating Range

    8. Operating Range Cooling Operation Range Continuous Operation Range Operation Range 25 27 Indoor temperature (˚C, WB) NOTE • In the range except for the continuous operation range, the protection control can be active depending on the heat source flow rate. (It is not a failure but a way of cycle protection against hot or cold water.) Heating Operation Range Warming up...
  • Page 35 1) Anti-freeze must be used when temperature of water inlet for heating is below 10°C or ground heat is used. Maintain approprate concentation level of anti-freeze according to temperature of water inlet. 2) Strict management of anti-freeze concentration level is required. Consult Samsung before application. Anti-freeze standard Type of anti-freeze (Based on 15°C)
  • Page 36 8. Operating Range Water Flow rate Water Flow Rate (LPM) Section 10HP 12HP 20HP 30HP Standard condition Operation range 48~96 58~115 68~137 114~228 170~342 AM080MXWA∗ AM200MXWA∗∗ AM100MXWA∗ AM120MXWA∗ 50.0 100.0 150.0 Water Flow rate of cooling water (L/min) Water Flow rate of cooling water (L/min) AM300KXWA∗∗...
  • Page 37: Piping Diagram

    9. Piping Diagram AM080/100/120MXWA∗∗ Ball Valve- High pressure Gas pipe (BV_HG) Check Valve- Main Cooling (CV_MC) Solenoid Thermistor- Valve- Water Main (T_W) Water Out Cooling (V_MC) Check Valve– Ball Valve- Heat Heat Exchanger- Heat Pump Recovery Main (BV_HP) (CV_HR) Water In (HX_M) Electronic Expansion...
  • Page 38 9. Piping Diagram AM200MXWA∗∗ Ball Valve- High pressure Gas pipe (BV_HG) Check Valve- Main Cooling (CV_MC) Solenoid Valve- Main Thermistor- Cooling Water Water Out (V_MC) (T_W) Check Valve– Heat Exchanger- Ball Valve- Heat Main Heat Pump Recovery (HX_M) (BV_HP) Water In (CV_HR) Electronic Fan Motor -...
  • Page 39 9. Piping Diagram AM300KXWA∗∗ Ball Valve- High pressure Gas pipe (BV_HG) Check Valve- Main Cooling (CV_MC) Solenoid Valve- Thermistor- Main Water Cooling Water Out (T_W) (V_MC) Heat Exchanger- Electronic Main Expansion Check Valve– (HX_M) Water In Valve–Main1 Ball Valve- Heat (E_M1) Heat Pump Recovery...
  • Page 40: Installation

    10. Installation Electrical wiring work Specification of the circuit breaker and power cable Power Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord. (Code designation IEC:60245 IEC 66 / CENELEC: H07RN-F) ※...
  • Page 41 10. Installation Caution for electrical work CAUTION • You must install ELCB or MCCB + ELB ‐ ELCB: Earth leakage breaker ‐ MCCB: Molded case circuit breaker ‐ ELB: Earth leakage breaker • Do not operate the outdoor unit before completing the refrigerant pipe work. •...
  • Page 42 10. Installation Specification of the protection tube Name Temper grade Applicable conditions When the protection tube is installed indoor and not exposed Flexible PVC conduit to outside, because it is embedded in concrete structure Class 1 flexible When the protection tube is installed indoor but exposed to Galvanized steel sheet conduit outside so there are risk of damage to the protection tube...
  • Page 43 10. Installation Connecting the power terminal ▶ Connect the cables to the terminal board with solderless ring terminals. ▶ Properly connect the cables by using certified and rated cables and make sure to fix them properly so that external force is not applied to the terminal. ▶...
  • Page 44 10. Installation Installing the Solution device ▶ When the number of indoor units installed with the outdoor unit is 16 or less Solution device terminal Communication cable terminal (Outdoor unit ~ Outdoor unit) Communication cable terminal (Outdoor unit ~ Indoor unit) ※...
  • Page 45 10. Installation When the water pipe passes through back of the product (Unit : mm) Outdoor Space for unit installing water pipe Service space Front side Anti-vibration pad <Top view> <Front view> Module or continuous installation (Unit : mm) Outdoor Outdoor unit unit...
  • Page 46 10. Installation Double installation (Unit : mm) H beam support Service space <Front view> ▶ For the double installation, service space is required for the front, rear, and sides of the product. For the size of the service space, refer to the service space size of single, module or continuous installation. ▶...
  • Page 47 10. Installation When installing multiple outdoor units at the same place, construct a H beam or an anti-vibration frame on the base ground to install the outdoor unit. 8. After installing a H beam or an anti-vibration frame, apply corrosion protection and other necessary coating. 9.
  • Page 48 10. Installation Refrigerant pipe installation • When installing, make sure there is no leakage. When collecting the refrigerant, stop the compressor first before removing the connection pipe. If the refrigerant pipe is not properly connected and the compressor CAUTION is working with the service valve open, the pipe sucks the air in which makes the pressure inside of the refrigerant cycle abnormally high which may lead to explosion and injury.
  • Page 49 10. Installation Selecting refrigerant pipe Y-joint Increase the main pipe size ▶ Install the refrigerant pipe according to main pipe size of each outdoor unit capacity. ▶ When the pipe length (including elbow) between the outdoor unit and the farthest indoor unit exceeds 90m, the size of the pipe (main pipe) connecting the outdoor unit to the first branch joint must be increased by one grade.
  • Page 50 10. Installation Pipe installation for an outdoor unit Please read the following instructions to connect the refrigerant pipe to an outdoor unit. ‐ For H/P System, connect liquid and gas pipes to an indoor unit. ‐ For HR System, connect liquid and high/low pressure gas pipes to a MCU. Close the internal heat pump valve and set the following option switch.
  • Page 51 10. Installation Refrigerant pipe installation 2. Connect refrigerant pipes between outdoor units. ▶ To connect pipes between outdoor units, branch joints (that needs to be purchased separate) must be installed. ※ For optimal distribution of the refrigerant, you must use Y-joint for connecting outdoor units. (Do not use T-joint) ▶...
  • Page 52 10. Installation Classification Example Remarks Installing only a+b+c+d+e+f+g+p ≤ 170 with Y-joint (190) m Installing with Equivalent Actual pipe 170 m and Y-joint and a+b+h ≤ 170 (190) m, length length below (190 distribution a+i+k ≤ 170 (190) m • Y-joint: 0.5 m (Equivalent m and header • Distribution length) below) Installing header: 1 m...
  • Page 53 10. Installation Note 1) Required condition Classification Condition Example 45 m ≤ b+c+d+e+f+g+p ≤ 90 m: Size of the First branch joint ~ branch pipe (b, c, d, e, f, g) must be increased Farthest Indoor unit by one grade If the size of the main pipe (pipe that connects between the outdoor unit ~ first branch joint) was not increased by one grade: a+(b+c+d+e+f+g)×2...
  • Page 54 10. Installation Connect to other outdoor unit ※ Use a provided liquid side socket according to the size of the selected pipe. Pipe Connect to other branch joint between outdoor units or outdoor Liquid side unit socket Liquid side socket Pipe Connect to other branch joint between outdoor units or main pipe branch joint...
  • Page 55 10. Installation Installing the indoor units Model MCU-S6NEK2N MCU-S4NEK3N MCU-S2NEK2N MCU-S1NEK1N Example installing (Each port connection) MCU series connection Example installing (MCU series connection) Under 16.0 kW indoor unit : Don’t use Y-connector This unit is only 16.0 kW ~ 28.0 kW indoor unit : Use Y-connector at the Gas & Liquid line connectable for one port under In case of using Y-connector, it is only connectable for port combination at below...
  • Page 56 10. Installation How to connect the pipes 70 mm Protect with wet towel when welding 70 mm Pipe connection from outdoor unit Default installing direction. Low pressure gas pipe conection (welding) High pressure gas pipe connection (welding) Liquid pipe connection (welding) Pipe connection to indoor unit Liquid pipe (welding) Gas pipe (welding)
  • Page 57 Note 1): Anti-freeze must be used when temperature of water inlet for heating is below 10°C or ground heat source is used. Maintain appropriate concentration level of anti-freeze according to temperature of water inlet. Note 2): Strict management of anti-freeze concentration level is required. Consult Samsung before application. Note 3): When inlet water temperature is outside of limit, consult Samsung before application.
  • Page 58 10. Installation Diameter of the outdoor unit connection part where water pipe will be connected is 32A. If you install outdoor units with different capacities, install a flow control valve to secure rated flow for each outdoor unit. Socket must be connected within below tightening torque. If the tightening torque exceeds below value, it may cause product breakage.
  • Page 59 10. Installation Ball valve Auto air discharge valve (used as cleaning hole) Cleaning device Ground heat Water outlet pipe or closed Plate circuit Strainer for outdoor unit cooling type heat tower exchanger Water inlet pipe Strainer for Ball valve pump Outdoor unit (used as cleaning hole) Flushing pipe...
  • Page 60: Accessory

    11. Accessory Controller Classification Product Model Image Remark Using Wireless Remote MR-EH00 DVM, CAC Controller Wireless Remote AR-KH00E 360 CST Only DVM, CAC Controller Wired Remote MWR-WE11N DVM, CAC Controller Wired Remote Controller MWR-SH00N DVM, CAC - Simple Type Wired Remote Controller MWR-SH10N DVM, CAC...
  • Page 61 11. Accessory Classification Product Model Image Remark Using Onoff Controller MCM-A202DN DVM, CAC Touch Centralized MCM-A300N DVM, CAC Controller WIFI KIT MIM-H03N DVM, CAC Centralized Control System Interface Module MIM-N01 DVM, CAC ERV Interface MIM-N10 DVM, CAC Module DMS2.5 MIM-D01AN DVM, CAC Integrated management...
  • Page 62 Operation Mode MCM-C200 Selection Switch Others Module Controller MCM-A00N CHILLER Only CHILLER FCU Interface MIM-F10N CHILLER Only CHILLER Module NOTE • In case you want more information about the accessories, please refer to the control and accessories TDB on pvi.Samsung.com site.
  • Page 63 DVM, CAC Test run Solution External Room Sensor MRW-TA MRW-TA DVM, CAC Others Operation Mode Selection Switch MCM-C200 MCM-C200 NOTE • In case you want more information about the accessories, please refer to the control and accessories TDB on pvi.Samsung.com site.
  • Page 64 MXD-E32K200A MXD-E24K232A MXD-E24K300A 3 Indoor MXD-E32K224A MXD-E32K300A MXD-A38K2A 8~12 HP PDM KIT MXD-A12K2A 14~16 HP MXD-A58K2A 18~26 HP NOTE • In case you want more information about the accessories, please refer to the control and accessories TDB on pvi.Samsung.com site.
  • Page 65 11. Accessory Product Image Model Remark PC1NUSMAN 1Way CST (JSF-1) PC1NUPMAN 1Way CST (JSF-1) (Z-sliding) PC1MWSKAN 1Way CST (JSF-0) PC1NWSMAN 1Way CST (JSF-1) PC1BWSMAN 1Way CST (JSF-2) PC2NUSMEN 2Way Cassette PC4SUSMAN 4Way Cassette S (600x600) (Waffle) PC4SUSMEN 4Way Cassette S (600x600) (Classic) PC4NUSKAN 4way Cassette S (Waffle) Panel...
  • Page 66 X 4 EA Transformer for variable flow control Valve Transformer kit MVR-TK024 Input/Output : AC 220V/AC 24V, 10VA NOTE • In case you want more information about the accessories, please refer to the control and accessories TDB on pvi.Samsung.com site.
  • Page 67 5Hp's AHU MXD-K075AN only for 7.5Hp's AHU AHU-KIT MXD-K100AN only for 10Hp's AHU only for 10~40Hp's MCM-D201N NOTE • In case you want to know more information the accessories, please refer to the control and accessories TDB on pvi.samsung.com site...
  • Page 68 Ver. 1.01 Samsung Electronics Co., LTD. B2B PM / SE Head Office (Suwon Korea) 129, Samsung-Ro, Yeongtong-Gu, Suwon City, Gyeonggi-Do, Korea 16677 Website : www.samsung.com, http://btsp.samsunggsbn.com Email : airconditioner@samsung.com Images and data in this book may subject to change without prior notice.