Key Options
8-4 How to check the view mode using a tact switch (cont.)
AM080/100/120/200FXWASS
Optional item
Input unit SEG1 SEG2 SEG3 SEG4
Rotation defrost
Main
(HR only)
Expand operational
temperature range
Main
for cooling operation
Channel address
Main
Snow accumulation
Main
prevention control
Unused option
Main
Unused option
Main
Speed operatin
Main
Current restriction
Individual
rate
Oil collection
Main
interval
Disable
Main
Disable
Individual
Disable
Main
Setting highhead
Main
condition
Samsung Electronics
0
0
1
1
0
1
0
0
1
2
0
1
A
U
Automatic setting (Factory default)
1
3
0~15
Manual setting for channel 0~15
0
0
1
4
0
1
1
5
0
0
1
6
0
0
0
0
1
7
0
1
0
0
0
1
0
2
0
3
0
4
0
5
0
3
0
6
0
7
0
8
0
9
1
0
1
1
0
0
0
4
0
1
0
0
0
5
0
1
0
0
0
6
0
1
0
0
0
1
0
7
0
2
0
3
0
0
0
1
type 1 (Indoor unit is lower than outdoor
0
8
0
2
type 1 (Indoor unit is lower than outdoor
0
3
(Outdoor unit is lower than indoor unit)
Function of the option
Disabled (Factory default)
Enabled
Disabled (Factory default)
Enabled
Enabled (Factory default)
Disabled
Unused option
Unused option
Disabled(Factory default)
Enable
100% (Factory default)
95 %
90 %
85 %
80 %
75 %
70 %
65 %
60 %
55 %
50 %
No restriction
Factory default
Shorten the interval by 1/2
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable (Factory default)
Level 1 of height difference
unit)
Level 2 of height difference
unit)
Height difference type 2
Remarks
When enabled, continuous heating
operation is possible but heating
performance will decrease during
rotation defrost operation
When enabled, continuous
cooling operation is possible even
in low temperature condition up
to -15?C, but noise of the MCU will
increase
Address for classifying the product
from upper level controller (DMS,
S-NET 3, etc.)
During snow accumulation
prevention, the fan mayspin even
when the unit is not in operation
Unused option option
by this model
Unused option option
by this model
Enabling this setting will
command the air conditioner to
cool/heat faster at initial start-up
However this function will not
wortk when High-head condition-
setting or Long-piping condition
setting is enabled.
When restriction option is
set, cooling and heating
performance may decrease.
This function is not applicable for
this model
This function is not applicable for
this model
This function is not applicable
for this model
When outdoor unit is over
40 ~
80 m above the indoor unit
When outdoor unit is over 80 m
above the indoor unit
When indoor unit is over 30 m
above the outdoor unit
395