Samsung AM080FX A Series Service Manual page 181

System air conditioner outdoor unit
Table of Contents

Advertisement

Troubleshooting
4-3 Appropriate Measures for Different Symptom (cont.)
4-3-35
: Suspension of starting by abnormal compression ratio
Outdoor unit
display
Duct, Cassette (1/2 Way),Console, Celing
Operation
Indoorunit
display
×
※ ● : ON ◑ : Flash ×: OFF
Judgment
∙ Compression ratio [(High pressure+1.03)/(Low pressure+1.03)] less than 1.5 and lasts for 10 minutes or more
Method
∙ Differential pressure (high pressure- low pressure) less than 0.4 MPa.g and lasts for 10 minutes or more
∙ Indoor and Outdoor EEV breakdown
Cause of
∙ 4Way Valve breakdown
problem
∙ High and Low pressure sensor defective
∙ Refrigerant shortage
1. Cause of problem
Auto Trial Operation
Is the S-net estimated value
and the Manifold Gauge value in range?
Are the 4Way Valve normally operating?
Are the Indoor Unit and Outdoor Unit EEV
normally operating?
Is current of compressor normally?
Complete
Samsung Electronics
Defrost
Timer
Fan
Filter/MPI
×
Yes
Yes
No
Yes
Cassette (4/Mini4 Way)
Operation Defrost
×
No
No
No
No
Wall-mounted (NeoForte)
Timer
Filter Operation
Timer
Replace defective sensor
Replace defective sensor
Check the 4Way Valve
Check the relevant EEV
Compressor Inspection
Check the refrigerant
Turbo
193

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents