Samsung AM080FX A Series Service Manual page 231

System air conditioner outdoor unit
Table of Contents

Advertisement

Troubleshooting
4-4 Case study for trouble shoots (cont.)
4-4-13 Case study – Poor cooling caused by IPM overheated (cont.)
- Conclusion : Change bolt to new one, reattach the IPM → Problem solved
Date
OD Temp
High pressure
Low pressure
Comp1
Comp2
Current1
Current2
IPM1
IPM2
※ IPM Temp Protection
- Hz Hold : 90℃
- Hz Down : 93℃
Samsung Electronics
5/28
5/29
38
38
30.5
30.4
10.9
11.4
52
52
55
55
12.3
15.3
10.3
14.2
86
89
89
81
Basic
Reattach #1
Date
6/5
OD Temp
41.6
High pressure
34.7
Low pressure
10.5
Comp1
61
Comp2
64
Current1
14.9
Current2
14.2
IPM1
88
IPM2
90
Reattach #2
※ HP Protection
- Hz Hold : 36 kgf/㎠
- Hz Down : 37 kgf/㎠
6/5
40.8
36.4
9.9
82
85
20.2
19.3
85
86
Solved