Samsung AM080FX A Series Service Manual page 50

System air conditioner outdoor unit
Table of Contents

Advertisement

Product Specifications
2-5 Product Specification (cont.)
2-5-1 Outdoor Unit (cont.)
Model Name
Power Supply
Mode
Performance
Capacity
(Nominal)
Power Input
(Nominal)
Current Input
(Nominal)
Running
Power
Current
Power
Consumption
MCA(Minimum Circuit Amps)
MFA/MOP(Maximum Fuse Amps)
Nominal Cooling 1)
COP
Nominal Heating 2)
Compressor
Oil
Fan
External Static
Pressure
High pressure gas pipe
Piping
Piping length
Connection
After branch
Total piping
length
Level
difference
Refrigerant
Factory Charging
Sound Pressure
Sound
External
Net Dimension (WxHxD)
Dimension
Shipping Dimension (WxHxD)
Operating
Temp. Range
Safety device
Item
1) Nominal cooling capacities are based on;
- Indoor temperature : 27°C DB, 19°C WB
- Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
2) Nominal heating capacities are based on;
- Indoor temperature : 20°C DB, 15°C WB
- Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
3) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
4) Sound power level is an absolute value that a sound source generates.
Sound pressure level is a relative value, depending on the distance and acoustic environment.
Sound values are obtained in an anechoic room.
Sound values of multi combination are theoretical values based on sound results of individual installed units.
5) These products contain R410A which is fluorinated greenhouse gas.
6) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
*PDM kit: Pressure Drop Modulation kit. When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
Samsung Electronics
Image
HP
Cooling
Heating
Cooling 1)
Heating 2)
Cooling 1)
Heating 2)
Cooling
Heating
Max
Cooling
Heating
ESEER
Type
Output
Model Name
Type
Initial Charge
Type
Output x n
Air Flow Rate
Max.
Liquid Pipe
Gas Pipe
ODU-IDU
Max.
Max.
System
Actual
Outdoor unit in
highest position
ODU-IDU
Indoor unit in
highest position
IDU-IDU
Max.
Type
Cooling
Heating
Sound Power
Net Weight
Shipping Weight
Cooling
Heating
1
2
3
4
AM140JXVAFH/AZ AM160JXVAFH/AZ AM180JXVAFH/AZ AM200JXVAFH/AZ
Φ, V, Hz
3,3,208-230,60
3,3,208-230,60
-
HEAT PUMP
HP
14
kW
40.0
Btu/h
136,500
kW
45
Btu/h
153,500
kW
8.47
9.18
A
24.70
26.80
A
24.70
26.80
50.00
kW
8.47
9.18
A
55.00
A
75.00
W/W
4.720
4.900
-
-
Scroll Inverter
Scroll Inverter
kW
5.18 x 2
-
DS-GB052FBVASG x 2 DS-GB052FBVASG x 2 DS4GJ5066EVASG x 2 DS4GJ5066EVASG x 2
-
PVE
cc
-
-
Propeller + BLDC
Propeller + BLDC
W
620 x 2
m³/min
255
l/s
4250
mmAq
8
Pa
78.45
Type
Braze connection
Braze connection
Φ, mm
12.7
Φ, inch
1/2"
Type
Braze connection
Braze connection
Φ, mm
28.58
Φ, inch
1+1/8"
Φ, mm
-
Φ, inch
-
m
200(220)
m
90
m
1000
m
110
m
110
m
50
-
R410A
kg
7.7
dB(A)
61
81
kg
292
kg
311
mm
1295x1695x765
1295x1695x765
mm
1363x1887x832
1363x1887x832
-5 ~ 48
-25 ~ 24
-
-
-
-
3,3,208-230,60
HEAT PUMP
HEAT PUMP
16
18
45.0
50.4
153,500
172,000
50.4
56.7
172,000
193,500
10.64
10.66
10.30
10.40
31.00
31.10
30.00
30.30
31.00
31.10
30.00
30.30
56.10
66.50
10.64
10.66
10.30
10.40
62.00
73.00
75.00
75.00
4.230
4.730
4.890
5.450
-
-
Scroll Inverter
5.18 x 2
6.45 x 2
PVE
PVE
-
-
Propeller + BLDC
620 x 2
620 x 2
255
260
4250
4333
8
8
78.45
78.45
Braze connection
12.7
15.88
1/2"
5/8"
Braze connection
28.58
28.58
1+1/8"
1+1/8"
-
-
-
-
200(220)
200(220)
90
90
1000
1000
110
110
110
110
50
50
R410A
R410A
7.7
8.4
63
64
83
86
300
300
319
319
1295x1695x765
1363x1887x832
-5 ~ 48
-5 ~ 48
-25 ~ 24
-25 ~ 24
High pressure switch
Fan driver overload protector
Inverter overload protector
PC board fuse
3,3,208-230,60
HEAT PUMP
20
56.0
191,100
63
215,000
11.45
12.70
33.40
37.00
33.40
37.00
73.00
11.45
12.70
80.00
90.00
4.890
4.960
-
Scroll Inverter
6.45 x 2
PVE
-
Propeller + BLDC
620 x 2
265
4417
8
78.45
Braze connection
15.88
5/8"
Braze connection
28.58
1+1/8"
-
-
200(220)
90
1000
110
110
50
R410A
8.4
65
87
300
319
1295x1695x765
1363x1887x832
-5 ~ 48
-25 ~ 24
52

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents