Samsung AM080FX A Series Service Manual page 385

System air conditioner outdoor unit
Table of Contents

Advertisement

Key Options
8-4 How to check the view mode using a tact switch (cont.)
AM140/160/180/200/220/240/260/280/300KXVSSSS
K4
(Number of press)
1 time
Order frequency (Compressor 1)
2 times
Order frequency (Compressor 2)
3 times
4 times
5 times
Discharge temperature (Compressor 1)
6 times
Discharge temperature (Compressor 2)
7 times
IPM temperature (Compressor 1)
8 times
IPM temperature (Compressor 2)
9 times
CT sensor value (Compressor 1)
10 times
CT sensor value (Compressor 2)
11 times
12 times
13 times
14 times
TOP temperature (Compressor 1)
15 times
TOP temperature (Compressor 2)
16 times
17 times
18 times
19 times
20 times
21 times
22 times
23 times
24 times
Current frequency (Compressor 1)
25 times
Current frequency (Compressor 2)
26 times
27 times
28 times
Address of master indoor unit
K4
(Number of
press)
Press and hold
the K4 to enter
the setting
1 time
2 times
3 times
4 times
5 times
6 times
7 times
Automatically assigned address of the
8 times
9 times
Manually assigned address of the units
Samsung Electronics
KEY operation
High pressure (MPa)
Low pressure (MPa)
Suction temperature
COND OUT temperautre
Temperature of liquid pipe
Outdoor temperature
EVI inlet temperature
EVI outlet temperature
Main EEV1 step
Main EEV2 step
EVI EEV step
HR EEV step
Fan step (SSR or BLDC)
Suction 2 temperature (H/R)
Master indoor unit address
Displayed content
Main version
Hub version
Inverter 1 version
Inverter 2 version
Fan 1 version
Fan 2 version
EEP version
units
K1 K2 K3 K4
Display on segment
Outdoor unit
model
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
Master indoor unit not selected → BLANK, N, D
S
If indoor unit No 1 is selected as the master unit → 0, 0, 1
Display on segment
page1
MAIN
HUB
INV1
INV2
FAN1
FAN2
EEP
SEG1
AUTO
Indoor unit: "A"
MCU: "C"
SEG4
MANU
Indoor unit: "A"
SEG2, 3, 4
AM160FXVSSSS → Off, 1, 6
120 Hz → 1, 2, 0
120 Hz → 1, 2, 0
1 52 MPa → 1, 5, 2
0 43 MPa → 0, 4, 3
87 °C → 0, 8, 7
87 °C → 0, 8, 7
87 °C → 0, 8, 7
87 °C → 0, 8, 7
2 A → 0, 2, 0
2 A → 0, 2, 0
-42 °C → -, 4, 2
-42 °C → -, 4, 2
-42 °C → -, 4, 2
-42 °C → -, 4, 2
-42 °C → -, 4, 2
-42 °C → -, 4, 2
-42 °C → -, 4, 2
-42 °C → -, 4, 2
2000 steps → 2, 0, 0
2000 steps → 2, 0, 0
300 steps → 3, 0, 0
300 steps → 3, 0, 0
13 steps → 0, 1, 3
120 Hz → 1,2,0
120 Hz → 1,2,0
-42 °C → -, 4, 2
page2
Version (ex 1412)
Version (ex 1412)
Version (ex 1412)
Version (ex 1412)
Version (ex 1412)
Version (ex 1412)
Version (ex 1412)
SEG2
Indoor unit: "0"
MCU: "1"
SEG5
Indoor unit: "0"
SEG3
Address
(ex: 07)
SEG6
Address
(ex: 15)
404

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents