Piping Diagram
7-3 Functions (cont.)
7-3-3 Others (cont.)
7-3-3-1 Field Setting (cont.)
Power mode: In cooling mode, the initial target low pressure is lowered to increase the compressor frequency increase
speed.
Input unit
Seg1
Main
1
▪ Notes
- Operating in energy saving mode, capacity might decrease compared to normal operation mode.
Samsung Electronics
Power mode enabled
Default
Target low pressure (8kgf/cm2,g by default)
Target low pressure
(6.5kgf/cm2,g if power mode is enabled)
Seg2
Seg3
0
0
0
0
Seg4
Energy control Operation
0
1
2
Disabled (default)
Energy saving
Power