Electrical Connection; Device Orientation; Adjustment Of The Display Contrast - Labom CV4110 Operating Instructions Manual

Pressure transmitter
Table of Contents

Advertisement

3.5

Electrical Connection

Complete the mechanical installation before you connect the device electrically.
Set up all electrical connections while the voltage supply is switched off.
Output (2-wire)
Permissible supply voltage
Permissible load
Circular connector M12
4
1
Pay attention to the following points regarding electrical connections via cable gland:
 The display can be dismounted as described in Chapter 3.4. Use a small screwdriver
to press the spring of the terminal block completely downwards before inserting the
cable. Otherwise, it is not possible to ensure a safe electrical connection.
 Do not forget to tighten the cable gland after the electrical connection is finalised.
3.6

Device orientation

The case can be turned in relation to the process connection as well as the display in relation
to the case.
Turning the case in relation to the process connection (±170°) allows to choose the position
of the electrical connection. Turning the display in relation to the case allows to choose the
viewing angle independently of the position of the electrical connection.
3.7

Adjustment of the Display Contrast

The display contrast can be adjusted.
Press and hold the ESC key and use the arrow keys to adapt the contrast.
The setting is saved and the contrast screen closes as soon as the ESC key is released.
BA_080_en_2022-01_11.02 Pressure transmitter PASCAL CV4
3
2
n.c.
Figure 1: Options for the electrical connection
4...20 mA (20...4 mA)
= 12...30 VDC
U
V
≤ (U
R
- 12 V) / 22 mA
B
V
Cable gland
Page 4/24