YASKAWA GPD315/V7-4X Technical Manual page 47

Table of Contents

Advertisement

Table 2-2. V/f Startup Procedure - Continued
DESCRIPTION
Set motor rated current.
(This can be obtained from
the nameplate of the motor.)
Set the V/f pattern.
Parameters n011 through
n017 set the V/f pattern. Table
5-4 in section 5.27 lists
recommended V/f patterns.
The numbers in parentheses
shown in the example below
are for a 460V / 60 Hz
variable torque application
(fan or pump).
Set Parameter n011-
Maximum output frequency.
(60.0 Hz)
KEY SEQUENCE
V
Press and hold
until n036 is
displayed on the digital operator.
DATA
ENTER
Then press
.
V
V
Use the
&
keys until the
number in the display matches the motor
rated current.
DATA
ENTER
Then press
.
V
Press and hold
until n011 is
displayed on the digital operator.
DATA
ENTER
Then press
.
V
V
Use the
&
keys until the
desired number is in the display.
DATA
ENTER
Then press
.
2-7